57
Function (Parameter) list
2
FUNCTIONS
Parameter List
Maintenance parameters
Additional parameters
Parameter for manufacturer setting
Func-
tion
Parame-
ters
Indi-
cation
Name Setting Range
Minimum
Setting
Incre-
ments
Factory
Setting
Refer
To:
Cus-
tomer
Setting
Maintenance function
H1 (503)
Maintenance
timer
0 to 999
1
(1000h)
0122
H2 (504)
Maintenance
timer alarm output
set time
0 to 999, - - -
1
(1000h)
36
(36000h)
122
H3 (555)
Current average
time
0.1 to 1s 0.1s 1s 123
H4 (556)
Data output mask
time
0 to 20s 0.1s 0s 123
H5 (557)
Current average
value monitor
signal output
reference current
0.1 to 999A 0.1A 1A 123
Func-
tion
Parame-
ters
Indi-
cation
Name Setting Range
Minimum
Setting
Incre-
ments
Factory
Setting
Refer
To:
Cus-
tomer
Setting
Additional
function
H6 (162)
Automatic restart
after instantaneous
power failure
selection
0, 1, 10 1 1 92
H7 (559)
Second electronic
thermal O/L relay
0 to 50A, - - - 0.1A - - - 69
Func-
tion
Parame-
ters
Indi-
cation
Name Setting Range
Minimum
Setting
Incre-
ments
Factory
Setting
Refer
To:
Cus-
tomer
Setting
b1 (560)
Parameter for manufacturer setting. Do not set.
b2 (561)

Table of Contents