6. 
WIRING 
- 
Items 
to 
60 
Checked 
when 
Designing  an 
Application 
(1) 
If 
the  application 
has 
a  commercial  power 
supply selector circuit as shown in the illustra- 
tion 
to 
the  right,  accidental  connection  of  line 
power 
to 
IIM 
inverter 
output 
terminals  will 
Power 
JjTFbF 
damage the inverter. 
To 
avoid 
this 
problem,  in- 
*' 
*__._______. 
terlock 
MC1 
and 
MC2 
both 
electrically  and 
mechanically. 
(2) 
At  an  occurrence 
01 
power interruption, il the start signal  (start 
switch) 
is 
retained 
ON 
with  the  frequency  instruction  retained,  the  inverter  will  restart  automaticaliy when 
power  is restored. 
It 
restarting 
of 
the 
inverter is not  desired  on 
poww 
restoration, 
it 
is 
necessary to  install  a 
magnetic 
contactor 
(MC) 
at 
the primary 
side 
of 
the 
inverter as 
well  as 
to 
design 
a 
control  sequence 
that 
disables  the 
s@rt 
signal. 
(3) 
Low  level  signals  are  used  in 
the 
control  circuit. 
Use 
dry contacts, 
hwo 
contacts ar- 
ranged  in  parallel,  or  a  twincontact 
to 
prevent  defective  wntecting. 
(4) 
Do 
not input voltage to contact input terminals 
(STF, 
for example) 
of 
the 
control  circuit, 
(5) 
Do 
not 
apply 
voltage directty to the 
alarm 
output 
signal 
terminals (A, 
8, 
C) 
without 
a 
relay 
coil or lamp. 
(6) 
If, 
according to  the  ap@cation, an  open  collector  output 
such 
as 
an 
output 
from  a 
programmable  controller  is  connected  directly 
to 
the 
inverter input  terminal,  use ter- 
minal 
PC 
(external  transistor  common). 
Acddaal 
connection 
IWMieI 
How 
to 
u.0 
trnnirui 
PC 
Connect the external power supply  common for  tramistor output signals 
to 
terminal 
PC 
to prevent  malfunctioning  due 
to 
undesirable  current. 
Note: 
For type 
AY40 
unit, 
it 
is necessary to  install 
24 
VDC 
power 
suppiy. 
-12-