11. 
OPERATION 
Note: 
1 
2 
3 
4 
5 
6 
After  turning 
ON 
the 
MRS 
terminal, if the  setting  for Pr.79 
is 
changed  to  any  value  other 
than '7"  in the PU operation mode,  the 
MRS 
terminal  functions  as  the  ordinary 
MRS 
terminal  (mechanical  reset  terminal)  instead 
of 
the  edit  enable  signal  terminal. Then the 
operation 
mode 
is  changed  according  to  the  new  setting  for  Pr.79. 
When  mode  changed  is  attempted  between  the  external  operation  mode  to  the  PU 
operation  mode  with  the 
MRS 
terminal 
ON, 
the  mode  change  will  not  occur 
if 
the STF 
or  STR  terminal  is 
ON. 
In  the  setting 
of 
Pr.79 
= 
7 with the 
MRS 
terminal 
ON, 
if  the 
MRS 
terminal  is  turned  OFF 
while in  the  PU operation  mode, the operation 
mode 
is  changed  to 
the 
external  opera- 
tion 
mode 
independent 
of 
the  OWOFF  status  of  the  terminal  (STF, 
STR). 
Therefore, 
if 
the 
MRS 
terminal 
is 
turned  OFF while either the STF  or STR terminal 
IS 
ON, 
the motor 
is  controlled  in the  external  operation  mode. 
During  the  operation  in  the  PU operation  mode,  the  ordinary 
MRS 
function  does  not 
work. 
When  the  mode  is  changed  from  the  PU operation  mode  to  the  external  operation 
mode  forcibly,  the  parameter unit is  internally  reset  once 
to 
secure the monitor  screen. 
If  an alarm  has  occurred,  the  inverter  can  be  reset  by  pressing  the  stop  key in the  PU 
operation mode. Resetting 
of 
the  inverter in the  external  operation  mode  is  not  possible. 
Therefore,  resetting  the  inverter  always changes  the  mode  to  the  PU operation mode. 
-36-