14 Test Operation, Adjustment, Maintenance and Troubleshooting
14.6 Judgment by Error Codes and Representation of Error Codes
11
High-Speed 
Counters
12
Output Wiring
13
Wiring for 
Various Uses
14
Test Run, 
Maintenance, 
Troubleshooting
15
IInput/Output 
Powered 
Extension Units
16
Input/Output 
Extension 
Blocks
17
Extension 
Power Supply 
Unit
18
Other Extension 
Units and 
Options
19
Display Module
20
Terminal Block
*1. The unit number 0 to 7 of the special function unit/block error is put in .
*2.
"
" indicates the following values for each special adapter/special block where an error has
occurred.
If an error has occurred in 2 or more special adapters/special blocks, "
" indicates the lowest unit
number among the special adapters/special blocks in which an error has occurred.
Operation error [M8067(D8067)]
6771
Continues
operation
Memory cassette is not connected.
Check whether the memory cassette is mounted 
correctly.
6772 Memory cassette is write protected.
The write-protect switch of the memory cassette was 
set to ON when data was transferred to the flash 
memory.
6773
Access error to flash memory during writing in RUN 
mode
While data was written in the RUN mode, data was 
transferred to (read from or written to) the flash 
memory.
Special block error [M8449 (D8449)]
020
*1
Continues 
operation
General data sum error
Verify that extension cables are correctly connected.
021
*1
General data message error
022
*1
System access error
025
*1
Access sum error in other station via CC-Link
026
*1
Message error in other station via CC-Link
030
*1
General data writing error to memory cassette
When the memory cassette is used, check whether 
it is mounted correctly.
If the problem persists, something may be 
malfunctioning inside the PLC. Consult your local 
Mitsubishi Electric representative.
080
*1
FROM/TO error
This error occurs in the execution of operation.
• Review the program and check the contents of 
the operands used in applied instructions.
• Verify that the specified buffer memories exist in 
the counterpart equipment.
• Verify that extension cables are correctly
connected.
090
*1
Peripheral equipment access error
• Check the cable connection between the 
programming panel (PP) / programming device 
and the PLC.
• Verify that extension cables are correctly 
connected.
Special parameter error [M8489 (D8489)]
01
*2
Continues 
operation
Special parameter setting time-out error
Turn OFF the power, and check the power supply 
and connection of special adapters/special blocks.
02
*2
Special parameter setting error
Special parameters are set improperly.
• Confirm troubleshooting for special adapters/
special blocks, and set special parameters 
correctly.
• Set special parameters correctly, turn OFF the
power, and then turn ON the power.
03
*2
Special parameter transfer target unconnected 
error
Special parameters are set, but special adapters/
special blocks are not connected.
Check whether special adapters/special blocks
are connected.
04
*2
Special parameter unsupported function
Check that special parameters with unsupported
settings are not set for connected special
adapters/special blocks.
Value of 
 (decimal) Special adapter/special block where an error has occurred
00 Special block (Unit number 0)
10 Special block (Unit number 1)
20 Special block (Unit number 2)
30 Special block (Unit number 3)
40 Special block (Unit number 4)
50 Special block (Unit number 5)
60 Special block (Unit number 6)
70 Special block (Unit number 7)
81 Special adapter (Communication channel 1)
82 Special adapter (Communication channel 2)
Error 
code
PLC operation at 
error occurrence
Contents of error Action