Mitsubishi MUH-GA50VB - When OPERATION INDICATOR lamp flashes 6-time.; Check of outdoor thermistor

Mitsubishi MUH-GA50VB
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Check of outdoor thermistor
Measure
resistance
between CN 661
1 and 2.
Measure
resistance
between CN 662
3 and 4.
No
Ye s
Replace the
thermistor.
Measure
resistance
between CN 662
1 and 2.
Connect CN661 and
CN662.
Turn ON the power
supply and press
the EMERGENCY
OPERATION switch.
Does the resistance
of thermistor have the
characteristics
on 10-5?
No
Ye s
Does the unit operate
10 minutes or more?
Replace the deicer P.C.
board.
Ok W.
W It is thought defective contact of the connector.
Turn OFF the
power supply.
<MUH-GA80VB>
Discharge temperature
thermistor(RT62)
<MUH-GA80VB>
Ambient temperature
thermistor(RT63)
Defrost thermistor(RT61)
When OPERATION INDICATOR lamp flashes 6-time.
Thermistors in the outdoor unit are abnormal.
F
w Disconnect the connectors CN661 and/ or CN662 from the deicer P.C. board.
(Check the characteristics of each thermistor.)