SYMBOL
C
CN1<R.B>
CN2<R.B>
CN2L<I.B>
CN27<I.B>
CN51<I.B>
F1,2<I.B>
I.B
J1
J5
J9
LED1<I.B>
LED2<I.B>
MF
MV
R.B
NAME
FAN MOTOR CAPACITOR
CONNECTOR (PROGRAM TIMER)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (LOSSNAY)
CONNECTOR (DRAIN LIFT-UP MECHANISM)
CONNECTOR (CENTRALLY CONTROL)
FUSE (6A 250V)
INDOOR CONTROLLER BOARD
JUMPER RESISTORS (MODE SELECTOR)
JUMPER RESISTORS (MODEL SELECTOR)
JUMPER RESISTORS (MODEL SELECTOR)
LED (DC 12V POWER)
LED (DC 5V POWER)
FAN MOTOR
VANE MOTOR
REMOTE CONTROLLER BOARD
SYMBOL
RT1
RT2
SW2<I.B>
SW3<I.B>
SW6<I.B>
SW7<I.B>
SW17<R.B>
SW18<R.B>
T
TB2
TB4
TB5,6
X4<I.B>
ZNR
NAME
ROOM TEMP.THERMISTOR
(32˚F/15k", 77˚F/5.4k" DETECT)
PIPE TEMP.THERMISTOR
(32˚F/15k", 77˚F/5.4k" DETECT)
SWITCH (ADDRESS SELECTOR)
SWITCH (EMERGENCY OPERATION)
SWITCH (MODEL SELECTOR)
SWITCH (MODEL SELECTOR)
SWITCH (ADDRESS SELECTOR)
SWITCH (FUNCTION SELECTOR)
TRANSFORMER
TERMINAL BLOCK (POWER)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE)
RELAY(FAN MOTOR)
VARISTOR
NOTES :
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
3. Symbols used in wiring diagram above are, : Connector. : Terminal block.
4. Emergency operation
If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I. B>) on the
indoor controller board.
[Check items]
(1) Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation. (If any trouble exists the
outdoor unit error code "P8" will be displayed on the remote controller and the trouble position will be shown on the outdoor controller board LED.
See electric wiring diagram of the outdoor unit for details.)
(2) Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1) Set the dip switch (SW3<I. B>) on the indoor controller board to 1 on and 2 off for cooling.
(2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker, in this order.
(3) During emergency operation, indoor fan runs at high speed but automatic vane remains stop. If vane is closed, open the vane by hands.
(4) Thermostat will not function.
(5) Emergency cooling should be limited to 10 hours maximum.
(6) After every operation, set all dip switches (SW3<I. B>) to OFF.