EasyManua.ls Logo

Mitsubishi PKFY-P63VKM-E.TH - Refrigerant System Diagram; Troubleshooting

Mitsubishi PKFY-P63VKM-E.TH
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1919
TROUBLESHOOTING
8
7
REFRIGERANT SYSTEM DIAGRAM
8-1. HOW TO CHECK THE PARTS
PKFY-P63VKM-E.TH PKYF-P100VKM-E.TH
PKFY-P63VKM-ER1.TH PKFY-P100VKM-ER1.TH
Parts name Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10 - 30)
Disconnect the connector then measure the resistance valve with a tester.
(Coil temperature 20)
Vane motor (MV)
Linear expansion
valve (LEV)
Refer to the next page for the details.
Room temperature
thermistor (TH21)
Liquid pipe temperature
thermistor (TH22)
Gas
pipe temperature
thermistor (TH23 ,24)
Normal
4.3k~9.6k
Abnormal
Open or short
Normal
200 ± 10%
Abnormal
(1)-(5)
White-Red
(2)-(6)
Yellow-Brown
(3)-(5)
Orange-Red
(4)-(6)
Blue-Brown
Open or short
Measure the resistance between the terminals with a tester. (Coil temperature 20)
Normal
250 ± 7%
Abnormal
-
Brown-Red
-
Brown-Orange
-
Brown-Yellow
-
Brown-Green
Open or short
Fan motor (MF)
Red
Yellow
Brown
Orange
Green
Connect pin No.
M
1
2
3
4
5
6
LEV
White
Yellow
Orange
Blue
Red
Brown
CN60
Refer to 8-1-3.
Strainer (#50mesh)
Strainer (#100mesh)
Strainer1 (#50mesh)
Strainer2 (#100mesh)
Heat exchanger
Room temparature thermistor TH21
Gas pipe thermistor (1) TH23
Liquid pipe thermistor TH22
Linear expansion valve
Gas pipe
Liquid pipe
Flare connection
Gas pipe
Liquid pipe
PKFY-P63VKM-E PKFY-P100VKM-E
:15.88 (5/8)
:9.52 (3/8)
:15.88 (5/8)
:9.52 (3/8)
Item
Model
Unit : mm (inch)
Gas pipe thermistor (2) TH24
PKFY-P63VKM-E.TH PKYF-P100VKM-E.TH
PKFY-P63VKM-ER1.TH PKFY-P100VKM-ER1.TH
OCH447B