13
6 DATA
6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
6-2. COMPRESSOR TECHNICAL DATA
Service Ref.
Piping length (one way)
Initial
charged
10 m 20 m 30 m 40 m 50 m 60 m 75 m
PUHZ-SW75VHA(-BS).UK
PUHZ-SW75VHAR3(-BS).UK
3.2 3.6 4.0 4.6 — — — 3.2
PUHZ-SW75VHAR4(-BS).UK 3.2 3.35 3.5 4.1 — — — 3.2
PUHZ-SW100VHA(-BS).UK
PUHZ-SW100VHAR3(-BS).UK
PUHZ-SW100YHA(-BS).UK
PUHZ-SW100YHAR1(-BS).UK
PUHZ-SW100YHAR3(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.4 4.6
PUHZ-SW100V/YHAR4(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.5 4.6
PUHZ-SW120VHA(-BS).UK
PUHZ-SW120VHAR3(-BS).UK
PUHZ-SW120YHA(-BS).UK
PUHZ-SW120YHAR1(-BS).UK
PUHZ-SW120YHAR3(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.4 4.6
PUHZ-SW120V/YHAR4(-BS).UK
4.6 4.8 5.0 5.6 6.2 6.8 7.5 4.6
U-V
U-W
W-V
Service Ref.
Compressor model
Winding
Resistance
( " )
U-V
U-W
W-V
Service Ref.
Compressor model
Winding
Resistance
( " )
ANB33FNEMT
(at 20°C)
(at 20°C)
0.19
0.19
0.19
PUHZ-SW100VHA.UK
PUHZ-SW100VHAR3.UK
PUHZ-SW100VHAR4.UK
PUHZ-SW100VHA-BS.UK
PUHZ-SW100VHAR3-BS.UK
PUHZ-SW100VHAR4-BS.UK
SNB220FAGMC-L1
0.95
0.95
0.95
PUHZ-SW75VHAR4.UK
PUHZ-SW75VHAR4-BS.UK
ANB33FNDMT
0.30
0.30
0.30
ANB42FNDMT
ANB42FNEMT
0.30
0.30
0.30
TNB220FLHMT
0.88
0.88
0.88
PUHZ-SW75VHA.UK
PUHZ-SW75VHAR3.UK
PUHZ-SW75VHA-BS.UK
PUHZ-SW75VHAR3-BS.UK
PUHZ-SW100YHA.UK
PUHZ-SW100YHAR1.UK
PUHZ-SW100YHAR3.UK
PUHZ-SW100YHAR4.UK
PUHZ-SW100YHA-BS.UK
PUHZ-SW100YHAR1-BS.UK
PUHZ-SW100YHAR3-BS.UK
PUHZ-SW100YHAR4-BS.UK
PUHZ-SW120YHA.UK
PUHZ-SW120YHAR1.UK
PUHZ-SW120YHAR3.UK
PUHZ-SW120YHAR4.UK
PUHZ-SW120YHA-BS.UK
PUHZ-SW120YHAR1-BS.UK
PUHZ-SW120YHAR3-BS.UK
PUHZ-SW120YHAR4-BS.UK
PUHZ-SW120VHA.UK
PUHZ-SW120VHAR3.UK
PUHZ-SW120VHAR4.UK
PUHZ-SW120VHA-BS.UK
PUHZ-SW120VHAR3-BS.UK
PUHZ-SW120VHAR4-BS.UK
0.19
0.19
0.19
Additional charge is required for pipes
longer than 10 m.