5 SPECIFICATIONS
<Reference data> Plate heat exchanger (ACH70-40 plates)
Nominal water ow L/min 22.9
Heating
(A7/W35)
Capacity kW 8.00
COP 4.40
Power input kW 1.82
Heating
(A7/W45)
Capacity kW 8.00
COP 3.40
Power input kW 2.35
Heating
(A2/W35)
Capacity kW 7.50
COP 3.40
Power input kW 2.20
Heating
(A2/W45)
Capacity kW 7.50
COP 2.83
Power input kW 2.65
Nominal water ow L/min 18.9
Cooling
(A35/W7)
Capacity kW 6.60
EER 2.55
Power input kW 2.59
Cooling
(A35/W18)
Capacity kW 7.10
EER 4.01
Power input kW 1.77
Rating conditions
Nominal operating condition
Heating (A7/W35)
Outside air temperature (Dry-bulb) + 7°C
Outside air temperature (Wet-bulb) + 6°C
Water temperature (inlet/outlet) + 30°C/+ 35°C
Heating (A7/W45)
Outside air temperature (Dry-bulb) + 7°C
Outside air temperature (Wet-bulb) + 6°C
Water temperature (inlet/outlet) + 40°C/+ 45°C
Heating (A2/W35)
Outside air temperature (Dry-bulb) + 2°C
Outside air temperature (Wet-bulb) + 1°C
Water temperature (inlet/outlet) + 30°C/+ 35°C
Heating (A2/W45)
Outside air temperature (Dry-bulb) + 2°C
Outside air temperature (Wet-bulb) + 1°C
Water temperature (inlet/outlet) + 40°C/+ 45°C
Cooling (A35/W7)
Outside air temperature (Dry-bulb) + 35°C
Outside air temperature (Wet-bulb) + 24°C
Water temperature (inlet/outlet) + 12°C/+ 7°C
Cooling (A35/W18)
Outside air temperature (Dry-bulb) + 35°C
Outside air temperature (Wet-bulb) + 24°C
Water temperature (inlet/outlet) + 23°C/+ 18°C
Note: "COP" and "Power input" in the above table do NOT
contain the "pump input (based on EN 14511)".
Nominal water ow L/min 32.1
Heating
(A7/W35)
Capacity kW 11.2
COP 4.45
Power input kW 2.51
Heating
(A7/W45)
Capacity kW 11.2
COP 3.42
Power input kW 3.27
Heating
(A2/W35)
Capacity kW 10.0
COP 3.32
Power input kW 3.02
Heating
(A2/W45)
Capacity kW 10.0
COP 2.66
Power input kW 3.76
Nominal water ow L/min 26.1
Cooling
(A35/W7)
Capacity kW 9.10
EER 2.75
Power input kW 3.31
Cooling
(A35/W18)
Capacity kW 10.0
EER 4.35
Power input kW 2.30
PUHZ-SW75VHA(-BS).UK
PUHZ-SW75VHAR3(-BS).UK
PUHZ-SW100VHA(-BS).UK PUHZ-SW100VHAR3(-BS).UK
PUHZ-SW100YHA(-BS).UK PUHZ-SW100YHAR1/R3(-BS).UK
PUHZ-SW120VHA(-BS).UK PUHZ-SW120VHAR3(-BS).UK
PUHZ-SW120YHA(-BS).UK PUHZ-SW120YHAR1/R3(-BS).UK
Nominal water ow L/min 45.9
Heating
(A7/W35)
Capacity kW 16.0
COP 4.10
Power input kW 3.90
Heating
(A7/W45)
Capacity kW 16.0
COP 3.23
Power input kW 4.95
Heating
(A2/W35)
Capacity kW 12.0
COP 3.24
Power input kW 3.70
Heating
(A2/W45)
Capacity kW 12.0
COP 2.52
Power input kW 4.76
Nominal water ow L/min 35.8
Cooling
(A35/W7)
Capacity kW 12.5
EER 2.32
Power input kW 5.38
Cooling
(A35/W18)
Capacity kW 14.0
EER 4.08
Power input kW 3.43
OCH533D