121
8. Removing the 4-way valve coil (21S4), linear expansion
valve coil (LEV-A) and bypass valve coil (SV)
(1)Removetheservicepanel.(SeeFigure1)
(2)Removethetoppanel.(SeeFigure1)
(3)Removetheelectricalpartsbox.(SeePhoto3)
[Removing the 4-way valve coil]
(4)Remove4-wayvalvecoilfixingscrew(M4×6).
(5)Removethe4-wayvalvecoilbyslidingthecoiltowardyou.
(6)Disconnecttheconnector21S4(green)onthecontroller
boardintheelectricalpartsbox.
[Removing the linear expansion valve coil]
(4)
Removethelinearexpansionvalvecoilbyslidingthecoilupward.
(5)Disconnecttheconnectors,LEV-A(white),onthecontroller
circuitboardintheelectricalpartsbox.
[Removing the bypass valve coil]
(4)Removethebypassvalvecoilfixingscrew(M4×6).
(5)Removethebypassvalvecoilbyslidingthecoilupward.
(6)DisconnecttheconnectorSV2(blue)onthecontroller
circuitboardintheelectricalpartsbox.
9. Removing the 4-way valve
(1)Removetheservicepanel.(SeeFigure1)
(2)Removethetoppanel.(SeeFigure1)
(3)Removetheelectricalpartsbox.(SeePhoto3)
(4)Remove3valvebedfixingscrews(4×10),4ballvalve
andstopvalvefixingscrews(5×16),thenremovethe
valvebed.
(5)Remove3rightsidepanelfixingscrews(5×12)intherear
oftheunitandthenremovetherightsidepanel.
(6)Removethe4-wayvalvecoil.(SeePhoto8)
(7)Recoverrefrigerant.
(8)Removetheweldedpartof4-wayvalve.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the 4-way valve, cover it with a wet
cloth to prevent it from heating (250˚F or more), then
braze the pipes so that the inside of pipes are not
oxidized.
10. Removing the linear expansion valve
(1)Removetheservicepanel.(SeeFigure1)
(2)Removethetoppanel.(SeeFigure1)
(3)Removetheelectricalpartsbox.(SeePhoto3)
(4)Remove3valvebedfixingscrews(4×10),4ballvalve
andstopvalvefixingscrews(5×16),thenremovethe
valvebed.
(5)Remove3rightsidepanelfixingscrew(5×12)intherear
oftheunitandthenremovetherightsidepanel.
(6)Removethelinearexpansionvalve.(SeePhoto8)
(7)Recoverrefrigerant.
(8)Removetheweldedpartoflinearexpansionvalve.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the linear expansion valve, cover
it with a wet cloth to prevent it from heating (250˚F
or more), then braze the pipes so that the inside
of pipes are not oxidized.
Photo 8
Photo 9
Bypassvalve
coilfixing
screw
4-way
valve
4-wayvalvecoil
Linearexpansion
valvecoil(LEV-A)
4-wayvalve
Bypass
valve
coil(SV)
Linearexpansion
valvecoil(LEV-A)
Linearexpansion
valve
OPERATING PROCEDURE
PHOTOS
OCH577A