E3
or
E5
(6201,
6203)
Remote controller transmission error (E3)/
signal receiving error (E5)
1Abnormalifremotecontrollercouldnot
findblankoftransmissionpathfor6
secondsandcouldnottransmit.
(Checkcode:E3)
2Remotecontrollerreceivestransmitted
dataatthesametime,comparesthe
data,andwhendetectingit,judges
differentdatatobeabnormal30
continuoustimes.(Checkcode:E3)
1Abnormalifindoorcontrollerboardcould
notfindblankoftransmissionpath.
(Checkcode:E5)
2Indoorcontrollerboardreceives
transmitteddataatthesametime,
comparesthedata,andwhendetecting
it,judgesdifferentdatatobeabnormal
30continuoustimes.(Checkcode:E5)
1Setaremotecontrollertomain,andthe
othertosub.
2Remotecontrollerisconnectedwithonlyone
indoorunit.
3Theaddresschangestoaseparatesetting.
4–6 Diagnoseremotecontroller.
a)
When“RCOK”isdisplayed,remote
controllershavenoproblem.
Turnthepoweroff,andonagaintocheck.
Whenbecomingabnormalagain,replace
indoorcontrollerboard.
b)When“RCNG”isdisplayed,replace
remotecontroller.
c)
When“RCE3”or“ERC00-66”isdisplayed,
noisemaybecausingabnormality.
12remotecontrolleraresetas
“main.”
(Incaseof2remotecontrollers)
2Remotecontrollerisconnected
with2indoorunitsormore.
3Repetitionofrefrigerant
address
4Defectivetransmittingreceiving
circuitofremotecontroller
5Defectivetransmittingreceiving
circuitofindoorcontrollerboard
6Noisehasenteredinto
transmissionwireofremote
controller.
E6
(6840)
Indoor/outdoor unit communication
error (Signal receiving error)
1Abnormalifindoorcontrollerboardcould
notreceiveanysignalnormallyfor6
minutesafterturningthepoweron.
2Abnormalifindoorcontrollerboardcould
notreceiveanysignalnormallyfor3
minutes.
3Considertheunitasabnormalunder
thefollowingcondition;When2ormore
indoorunitsareconnectedtoanout-
doorunit,indoorcontrollerboardcould
notreceiveasignalfor3minutesfrom
outdoorcontrollercircuitboard,asignal
whichallowsoutdoorcontrollercircuit
boardtotransmitsignals.
Note:CheckLEDdisplayonoutdoorcontroller
circuitboard.(ConnectA-Controlservice
tool(PAC-SG50ST))
RefertoEA–ECitemifLEDdisplaysEA–AC.
1Checkdisconnectingorloosenessofindoor/
outdoorunitconnectingwireofindoorunitor
outdoorunit.
Checkalltheunitsincaseoftwinindoorunit
system.
2–4
Turnthepoweroff,andonagaintocheck.
Ifabnormalitygeneratesagain,replace
indoorcontrollerboardoroutdoorcontroller
circuitboard.
5
Turnthepoweroff,anddetachfanmotorfromcon-
nector(CNF1,2).Thenturnthepoweronagain.
Ifabnormalityisnotdisplayed,replacefanmotor.
Ifabnormalityisdisplayed,replaceoutdoor
controllercircuitboard.
6CheckRS1onoutdoornoisefilterboardwith
tester.Ifopenisdetected,replacetheboard.
Note:Otherindoorcontrollerboardmayhave
defectincaseoftwinindoorunitsystem.
1Contactfailure,shortcircuitor
miswiring(conversewiring)of
indoor/outdoorunitconnecting
wire
2Defectivetransmittingreceiv-
ingcircuitofoutdoorcontroller
circuitboard
3Defectivetransmittingreceiving
circuitofindoorcontrollerboard
4Noisehasenteredintoindoor/
outdoorunitconnectingwire.
5Defectivefanmotor
6Defectiverushcurrentresistor
39
Check code
Abnormal point and detection method
Judgment and action
Case
E0
or
E4
(6831,
6834)
Remote controller transmission error
(E0)/signal receiving error (E4)
1Abnormalifmainorsubremotecontrol-
lercannotreceivenormallyanytrans-
missionfromindoorunitofrefrigerant
address“0”for3minutes.
(Checkcode:E0)
2Abnormalifsub-remotecontrollercould
notreceiveforanysignalfor2minutes.
(Checkcode:E0)
1Abnormalifindoorcontrollerboard
cannotreceiveanydatanormallyfrom
remotecontrollerboardorfromother
indoorcontrollerboardfor3minutes.
(Checkcode:E4)
2Indoorcontrollerboardcannotreceive
anysignalfromremotecontrollerfor2
minutes.(Checkcode:E4)
1Checkdisconnectionorloosenessofindoor
unitortransmissionwireofremotecontroller.
2Setoneoftheremotecontrollers“main”.
Ifthereisnoproblemwiththeactionabove.
3Checkwiringofremotecontroller.
•Totalwiringlength:max.500m[1640ft]
(Donotusecableo3ormore.)
•Thenumberofconnectingindoorunits:
max.16units
•Thenumberofconnectingremotecontrol-
ler:max.2units
Ifthecauseoftroubleisnotinabove1–3,
4Diagnoseremotecontrollers.
a)When“RCOK”isdisplayed,remotecon-
trollershavenoproblem.
Turnthepoweroff,andonagaintocheck.
Ifabnormalitygeneratesagain,replace
indoorcontrollerboard.
b)When“RCNG”isdisplayed,replace
remotecontroller.
c)When“RCE3”or"ERC00-66"isdis-
played,noisemaybecausingabnormality.
Note:
Iftheunitisnotnormalafterreplacing
indoorcontrollerboardingroupcontrol,
indoorcontrollerboardofaddress“0”may
beabnormal.
1Contactfailureattransmission
wireofremotecontroller
2Allremotecontrollersareset
as“sub”remotecontroller.In
thiscase,E0isdisplayedon
remotecontroller,andE4is
displayedatLED(LED1,LED2)
ontheoutdoorcontrollercircuit
board.
3Miswiringofremotecontroller
4Defectivetransmittingreceiving
circuitofremotecontroller
5Defectivetransmittingreceiving
circuitofindoorcontrollerboard
ofrefrigerantaddress“0”.
6Noisehasenteredintothe
transmissionwireofremote
controller.
E1
or
E2
(6832,
6833)
Remote controller control board
1Abnormalifdatacannotbenormally
readfromthenonvolatilememoryofthe
remotecontrollercontrolboard.
(Checkcode:E1)
2Abnormaliftheclockfunctionofremote
controllercannotbenormallyoperated.
(Checkcode:E2)
1Defectiveremotecontroller 1Replaceremotecontroller.