40
Check code
Abnormal point and detection method
Judgment and action
E9
(6841)
Indoor/outdoor unit communication
error (Transmitting error) (Outdoor unit)
(1)Abnormalif“0”receivingisdetected30
timescontinuouslythoughoutdoorcon-
trollercircuitboardhastransmitted“1”.
(2)Abnormalifoutdoorcontrollercircuit
boardcouldnotfindblankoftransmission
pathfor3minutes.
1Indoor/outdoorunitconnecting
wirehascontactfailure.
2Defectivecommunicationcircuit
ofoutdoorcontrollercircuitboard
3Noisehasenteredpowersupply.
4Noisehasenteredindoor/out-
doorunitconnectingwire.
1Checkdisconnectionorloosenessofindoor/
outdoorunitconnectingwire.
2–4 Turnthepoweroff,andonagainto
check.Replaceoutdoorcontrollercircuit
boardifabnormalityisdisplayedagain.
EF
(6607
or
6608)
Non defined check code
Thiscodeisdisplayedwhennondefined
checkcodeisreceived.
1Noisehasenteredtransmission
wireofremotecontroller.
2Noisehasenteredindoor/out-
doorunitconnectingwire.
3Outdoorunitisnotapower-
invertermodels.
12Turnthepoweroff,andonagaintocheck.
Replaceindoorcontrollerboardoroutdoor
controllercircuitboardifabnormalityis
displayedagain.
3Replaceoutdoorunitwithpower-invertertype
outdoorunit.
Case
Ed
(0403)
Serial communication error
1.Abnormalifserialcommunication
betweenoutdoorcontrollercircuitboard
andoutdoorpowercircuitboardis
defective.
1Breakingofwireorcontact
failureofconnectorCN2
betweentheoutdoorcontroller
circuitboardandtheoutdoor
powercircuitboard
2Breakingofwireorcontact
failureofconnectorCN4
betweentheoutdoorcontroller
circuitboardandtheoutdoor
powercircuitboard
3Defectivecommunicationcircuit
ofoutdoorpowercircuitboard
4Defectivecommunicationcircuit
ofoutdoorcontrollercircuitboard
foroutdoorpowercircuitboard
12CheckconnectionofeachconnectorCN2
andCN4betweentheoutdoorcontroller
circuitboardandtheoutdoorpowercircuit
board.
3Replaceoutdoorpowercircuitboard.
4Replaceoutdoorcontrollercircuitboard.
1Breakingofwireorcontact
failureofconnectorbetween
outdoorcontrollercircuitboard
andM-NETboard
2ContactfailureofM-NETboard
powersupplyline
3NoisehasenteredintoM-NET
transmissionwire.
2.Abnormalifcommunicationbetween
outdoorcontrollercircuitboardand
M-NETboardisnotavailable.
1 Checkdisconnection,looseness,orbreaking
ofconnectionwirebetweenoutdoorcontrol-
lercircuitboard(CNMNT)andM-NETboard
(CN5).
2Checkdisconnection,looseness,orbreaking
ofconnectionwirebetweenoutdoorcontrol-
lercircuitboard(CNMNT)andM-NETboard
(CND).
3CheckM-NETtransmissionwiringmethod.
E8
(6840)
Indoor/outdoor unit communication
error (Signal receiving error)
(Outdoor unit)
(1)Abnormalifoutdoorcontrollercircuit
boardcouldnotreceiveanythingnor-
mallyfor3minutes.
1Contactfailureofindoor/out-
doorunitconnectingwire
2Defectivecommunicationcircuit
ofoutdoorcontrollercircuitboard
3Defectivecommunicationcircuit
ofindoorcontrollerboard
4Noisehasenteredintoindoor/
outdoorunitconnectingwire.
1Checkdisconnectionorloosenessofindoor/
outdoorunitconnectingwireofindoororout-
doorunits.
2–4 Turnthepoweroff,andonagainto
check.Replaceindoorcontrollerboardor
outdoorcontrollercircuitboardifabnormal-
ityisdisplayedagain.