10 - 19
MELSEC-Q
10 HIGH-LEVEL POSITIONING CONTROL
10.4.2 Condition data setting examples
The following shows setting examples for "condition data".
(1) Setting the device ON/OFF as a condition
[Condition] Device "X0" (=QD75 READY) is OFF
Da.15 Da.16 Da.17 Da.18 Da.19
Condition target
Condition
operator
Address Parameter 1 Parameter 2
01
H
: Device X 08
H
: DEV=OFF – 0 –
(2) Setting the numeric value stored in the "buffer memory" as a
condition
[Condition]
The value stored in buffer memory addresses "800, 801" (=
Md.20
Current
feed value) is "1000" or larger.
Da.15 Da.16 Da.17 Da.18 Da.19
Condition target
Condition
operator
Address Parameter 1 Parameter 2
04
H
: Buffer memory
(2 words)
04
H
:
P1
800 1000
(3) Designating the axis and positioning data No. to be simultaneously
started in "simultaneous start"
[Condition]
Simultaneously starting "axis 2 positioning data No.3".
Da.15 Da.16 Da.17 Da.18 Da.19
Condition target
Condition
operator
Address Parameter 1 Parameter 2
05
H
: Positioning
data No.
20
H
: Axis 2
designation
High-order 16
bits "0003
H
"