EasyManua.ls Logo

Mitsubishi QJ71DN91 - Page 131

Mitsubishi QJ71DN91
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - 7 9 - 7
MELSEC-Q
9 TROUBLESHOOTING
Detection time period
Error
code
Error detection Description Corrective action
Master
function
Slave
function
07
H
QJ71DN91 No slave node has been set. • Set at least one slave node.
08
H
QJ71DN91
The total input data length of all slave nodes is
too long.
• Reduce the total input data length of all slave
nodes to 512 bytes or less.
09
H
QJ71DN91
The total output data length of all slave nodes is
too long.
• Reduce the total output data length of all slave
nodes to 512 bytes or less.
0A
H
QJ71DN91
The watchdog timeout action value in a
parameter is invalid.
• Set it to one of the following:
0000
H
, 0001
H
, 0002
H
or 0003
H
0B
H
QJ71DN91
The expected packet rate value in the buffer
memory is smaller than the production inhibit time
value.
• Change the value so that
the expected packet
rate value is greater than or equal to the
production inhibit time value.
0C
H
QJ71DN91
Flash ROM checksum error (parameter area for
the master function)
• Save the parameters again.
• Do not turn OFF the power or reset while saving
the parameters.
0D
H
QJ71DN91
Flash ROM checksum error (parameter area for
the slave function)
• Save the parameters again.
• Do not turn OFF the power or reset while saving
the parameters.
0E
H
QJ71DN91
Flash ROM checksum error (auto communication
start setting area)
• Save the parameters again.
• Do not turn OFF the power or reset while saving
the parameters.
0F
H
QJ71DN91 Flash ROM all clear error
• Clear all parameters again.
• Do not turn OFF the power or reset while
clearing all parameters.
10
H
QJ71DN91
The number of input points per slave node has
exceeded 256 bytes.
• Correct the number of input points per slave
node to 256 bytes or less.
11
H
QJ71DN91
The number of output points per slave node has
exceeded 256 bytes.
• Correct the number of output points per slave
node to 256 bytes or less.
15
H
QJ71DN91
The production inhibit time value was set to 0 ms
(setting value 1) in cyclic.
• Set the production inhibit time value to a value
other than 0 ms.
16
H
QJ71DN91
Slave nodes that were set by parameters are all
reserved nodes.
• Set the parameters according to the slave
nodes connected to the network.
80
H
QJ71DN91
The number of reception bytes of the slave
function is out of range.
• Set it within the range between 0 and 128
bytes.
81
H
QJ71DN91
The number of transmission bytes of the slave
function is out of range.
• Set it within the range between 0 and 128
bytes.
81
H
QJ71DN91
The numbers of transmission bytes and reception
bytes of the slave function are both set to 0.
• Set either the number of transmission bytes or
the number of reception bytes to a value other
than 0.
A0
H
QJ71DN91
The numbers of I/O points of both the master and
slave functions were set to 0 when both the
master and slave functions were used.
• Set the number of I/O points of the slave node
in a master function parameter.
• Set the number of transmission/reception bytes
in a slave function parameter.
(Be sure to set either the master function or
slave function.)

Table of Contents