94
-
'16 • SCM-T-199
CAUTION
Take care when carrying the unit by hand.
Iftheunitweightismorethan20kg,itmustbecarriedbytwoormorepersons.
Do not carry the unit by the plastic straps. Always use the carry handle.
Do not install the outdoor unit in a location where insects and small animals
can inhabit.
Insectsandsmallanimalscanentertheelectricalpartsandcausedamageresultinginreorper-
sonalinjury.Instructtheusertokeepthesurroundingsclean.
If the outdoor unit is installed at height, make sure that there is enough space
for installation, maintenance and service.
Insufcientspacecanresultinpersonalinjuryduetofallingfromtheheight.
Do not install the unit near the location where neighbours are bothered by
noise or air generating from the unit.
It can affect surrounding environment and cause a claim.
Do not install in the locations where unit is directly exposed to corrosive
gases (like sulphide gas, chloride gas), sea breeze or salty atmosphere.
It can cause corrosion of heat exchanger and damage to plastic parts.
Do not install the unit close to the equipments that generate electromagnetic
waves and/or high-harmonic waves.
Equipment such as inverters, standby generators, medical high frequency equipments and telecom-
munication equipments can affect the system, and cause malfunctions and breakdowns.
The system can also affect medical equipment and telecommunication equipment, and obstruct its
functionorcausejamming.
Do not install the unit in the locations where:
There are heat sources nearby.
Unit is directly exposed to rain or sunlight.
There is any obstacle which can prevent smooth air circulation from inlet and outlet side of the unit.
Unit is directly exposed to oil mist and steam such as kitchen.
•Chemicalsubstanceslikeammonia(organicfertilizer),calciumchloride(snowmeltingagent)and
acid (sulfurous acid etc.), which can harm the unit, will generate or accumulate.
Drain water can not be discharged properly.
TV set or radio receiver is placed within 1m.
Height above sea level is more than 1000m.
Itcancauseperformancedegradation,corrosionanddamageofcomponents,unitmalfunctionandre.
Dispose of all packing materials properly.
Packingmaterialscontainnailsandwoodwhichcancausepersonalinjury.
Keep the polybag away from children to avoid the risk of suffocation.
Do not put anything on the outdoor unit.
Objectmayfallcausingpropertydamageorpersonalinjury.
• Donottouchthealuminumnoftheoutdoorunit.
Aluminiumntemperatureishighduringheatingoperation.Touchingncancauseburn.
Do not touch any refrigerant pipe with your hands when the system is in operation.
During operation the refrigerant pipes become extremely hot or extremely cold depending on the op-
eratingcondition.Touchingpipescancausepersonalinjurylikeburn(hot/cold).
Install isolator or disconnect switch on the power source wiring in accor-
dance with the local codes and regulations.
TheisolatorshouldbelockedinOFFstateinaccordancewithEN60204-1.
1. ACCESSORIES AND TOOLS
Standard accessories (supplied with indoor unit)
(1) Installation board
1pc (4)
Tapping screws
(for installation board
ø4 X 25mm)
5pcs
(2) Wireless remote control
1pc (5)
Wood screws
(for remote control holder
ø3.5 X 16mm)
2pcs
(3) Remote control holder
1pc (6)
Batteries
[R03 (AAA, Micro) 1.5V]
2pcs
Locally procured parts
(a)
Sleeve (1pc)
(b)
Sealing plate (1pc)
(c)
Inclination plate (1pc)
(d)
Putty
(e)
Connecting cable
(f)
Drain hose (extension hose)
(g)
Piping cover
(for insulation of connection piping)
(h)
Clampandscrew(fornishing
work)
(i)
Electrical tape
Tools for installation Work
Plus headed driver Pipe cutter
Knife
Hole core drill (65mm in diameter)
Saw Wrench key (Hexagon) [4m/m]
Tape measure Flaring tool set*
Torque wrench
(14.0-42.0N·m (1.4-4.2kgf·m))
Gas leak detector*
Pipe bender
Plier Flare adjustment gauge
*DesignedspecicallyforR410A