Troubleshooting Guide10
Call for Heat – Unit Does Nothing
The below troubleshooting steps refer to situations where the green light on the control
board is OFF and 24 VAC is NOT present between Sec & Com on board:
Step 1: Check for loose connections.
Step 2: Check incoming power (115 VAC).
Step 3: If incoming power is correct, check for 24 VAC at the secondary
of the transformer.
If incoming voltage is correct and there is no voltage at the secondary, then
replace transformer.
For more information on how to replace transformer, please visit
www.youtube.com/modineHVAC.