One Flash – Pressure Switch Won’t Close
The below troubleshooting information is related to situations where the power
exhauster DOES cycle on:
Unit Sequence: Green light on, call for heat, 24 VAC at R & W, power exhauster
cycles on after approximately 30 seconds, Green light will give one ash.
When there is a one ash troubleshooting code, it is indicating that the
pressure switch is not closing within 30 seconds of the power exhauster
being energized.
Possible Causes:
Blockage in tubing to pressure or venting is not allowing for a proper vacuum to pull
pressure switch contacts closed. To solve this issue, troubleshoot the units venting.
Wire off pressure switch
24 VAC not coming from board
Defective pressure switch
If this is the case, verify the switch is defective and replace.
For more information, visit www.youtube.com/ModineHVAC and watch the
video on venting.