50 MCP15-500.9
BASE MODEL WEIGHTS
Table 50.1 - Approximate Base Model Weight - (lbs.)
Section Description
Cabinet Size
Section Description
Cabinet Size
B C D B C D
Base Unit
MPR07 2377
Heat Option k
Electric l
10 & 20kW 164 164
MPR10 2489 30 & 40kW 174 174 328
MPR13 2570 50 & 60kW 185 185
MPR15 2585 2710 70 & 80kW 195 195 348
MPR20 2685 2894 100kW 205 205
MPR26 2898 100 & 120kW 370
MPR30 2907 6464 140 & 160kW 390
MPR40 6656 200kW 410
MPR52 6974
Natural Gas
(Ratings with * are
available as LP)
150MBH * 128
MPR60 6974 200MBH * 154
Dampers
Fresh Air Only (Digit 7=D, E, F) 40 45 200 250MBH * 154
Fresh and Return Air (Digit 7=A, B, C, R) 80 95 362 300MBH * 234 256
Hot Gas
Reheat
MPR07, 10 22 400MBH * 234 308 308
MPR13 26 500MBH * 308 308
MPR15, 20 26 64 600MBH 313 468
MPR26 64 800MBH 468
MPR30 64 70 900MBH * 616
MPR40 70 1000MBH * 616
MPR52, 60 80 1200MBH 936
Supply Air
Fan
(Direct Drive)
ANPL 11”, 12” 34 1400MBH 936
ANPA 12” 35 1600MBH 936
ANPA 14” 51 175 MBH - 94% 158
ANPA 16” 57 57 225 MBH - 94% 160
ANPA 16” Dual 114 310 MBH - 94% 173
ANPA 20” 97 97 350 MBH - 90% 316
ANPA 25” 163 450 MBH - 90% 320 320
ANPA 25” Dual 326 620 MBH - 94% 346
Motors j
(most common)
1HP 29 29 29 850 MBH - 87% 628
1-1/2HP 37 37 37 950 MBH - 87% 628
2HP 40 40 40 1220 MBH - 87% 814
3HP 69 69 69 1420 MBH - 87% 814
5HP 84 84 84
Auxiliary Electric
Heat Adder lm
20kW 164 164
7-1/2HP 115 115 115 40kW 328
10HP 128 128 128
Integral
Energy
Recovery
Wheel Option
n
Energy Recovery
Wheel Section
None 0 0 0
15HP 211 211 211 28” Wheel (21=A) 1002
20HP 232 232 232 36” Wheel (21=B) 1041
Power Option
Deadfront
Disconnect
(pick one)
None 0 0 0 48” Wheel (21=C) 1200
60A & 100A 5 5 5 36” Wheel (21=F) 1013
200A 10 10 10 46” Wheel (21=G) 1088
400A 10 58” Wheel (21=H) 3083
600A 15 68” Wheel (21=J) 3224
Convenience Outlet
(pick one)
None 0 0 0 74” Wheel (21=K) 3348
Powered by Others 2 2 2 81” Wheel (21=L) 3403
Powered by Unit 40 40 40
Exhaust Air Fan
None 0 0 0
11” 114
16” 126
20” 148
ANPA 20” 97
ANPA 25” 163
ANPA 25” Dual 326
Motors j
(most common)
Refer to Supply Fan
Motor for comparable
weights
* *
Energy Wheel
Electric Preheat l
None 0 0 0
20kW Nominal 103 103
40kW Nominal 108
Inlet Hood (Ships loose for eld installation) 68 72 112
j Motors weights shown are for Open Drip Proof (ODP), 1800RPM motors and
are each. If the configuration is a dual fan design, mutliply the weight shown
by two.
k If equipped with the hot water heat option, please consult the Breeze
AccuSpec selection program for the option weight.
l 20kW electric heat is derated for 208V and 230V.
m Auxiliary Electric Heat weight adder is additive for certain Natural and
Propane Gas heat rating weights.
n For weights of Energy Recovery Module on C-Cabinet (if applicable), refer to
the latest revision of literature #MCP15-520.
For weights of the Power Exhaust Module (Units with Digit 7=C or F) or
Barometric Relief Damper Module (Units with Digit 7=R), please consult the
Breeze AccuSpec selection program for the option weight.
Weights shown are approximate and may not include all features included with the selected unit. For more specific weight totals for
the selected unit(s), refer to either the Breeze AccuSpec Submittal Package or the Order Detail.