GENERAL PERFORMANCE DATA
Table 17.1 - Performance — Propeller Models
➀ ➁
Table 17.2 - Motor Data and Total Unit Power Requirements — Propeller Models
Standard Model Number
PD 30 PD 50 PD 75 PD 100 PD 125 PD 150 PD 175 PD 200 PD 250 PD 300 PD 350 PD 400
Btu/Hr. Input 30,000 50,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr. Output 24,000 40,000 60,000 80,000 100,000 120,000 140,000 160,000 200,000 240,000 280,000 320,000
Entering Airflow (CFM) 440 740 1100 1460 1850 2180 2550 2870 3700 4460 4870 5440
Outlet Velocity 515 610 736 860 870 931 959 819 1053 1123 1068 1016
Air Temp. Rise (°F) 51 50 51 51 50 51 51 52 50 50 53 54
Max. Mounting Hgt.
(Ft) 7 9 12 14 14 16 17 15 19 21 20 19
Heat Throw (Ft)
(Max. Mtg. Hgt.) 25 33 41 49 51 55 59 51 67 74 70 69
Motor Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC PSC PSC
115/60/1 (PC01) 1/40 1/40 1/12 1/12 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
230/60/1 (PC02) 1/40 1/40 1/8 1/8 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
200-208/60/1 (PC03)
1/40 1/40 1/8 1/8 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
Unit Voltage 115/60/1 115/60/1 With Use of Transformer 208/60/1 230/60/1
Supply Voltage 115/60/1 208V 230V 460V 575V 208/60/1 230/60/1
Mtr. Mtr. Total Max KVA Total KVA Total KVA Total KVA Total Mtr. Mtr. Total Max Mtr. Mtr. Total Max
Amps Rpm Amps Watts Req. Amps Req. Amps Req. Amps Req. Amps Amps Rpm Amps Watts Amps. RPM Amps Watts
1/40 1.0 1550 1.3 160 0.50 2.4 0.25 1.09 .025 0.54 0.25 0.43 0.4 1550 0.6 125 0.4 1550 0.6 140
1/12 1.6 1625 1.9 230 0.50 2.4 0.25 1.09 .025 0.54 0.25 0.43 - - - - - - - -
1/8 2.3 1625 2.6 310 0.50 2.4 0.50 2.17 0.50 1.09 0.50 0.87 1.0 1625 1.2 250 1.0 1625 1.2 280
1/6 2.7 1075 3.0 370 0.50 2.4 0.50 2.17 0.50 1.09 0.50 0.87 1.5 1075 1.7 350 1.5 1075 1.7 390
1/3 5.4 1075 5.7 680 1.00 4.81 0.75 3.26 0.75 1.63 0.75 1.30 - - - - 2.5 1075 2.7 620
1/2 7.5 1075 7.8 940 1.00 4.81 1.00 4.35 1.00 2.17 1.00 1.74 - - - - 3.5 1075 3.7 850
Table 17.3 - Performance — Blower Models
➀ ➁
Standard Model Number
BD 50 BD 75 BD 100 BD 125 BD 150 BD 175 BD 200 BD 250 BD 300 BD 350 BD 400
Btu/Hr. Input 50,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr. Output 40,000 60,000 80,000 100,000 120,000 140,000 160,000 200,000 240,000 280,000 320,000
Entering Airflow (CFM ) 673 1010 1347 1684 2020 2357 2694 3367 4040 4714 5387
Outlet Velocity 560 681 799 799 869 892 773 966 1026 1037 1008
CFM Range 529-926 794-1389 1058-1852 1323-2315 1587-2778 1852-3241 2116-3704 2646-4630 3175-5556 3704-6481 4233-6584
Air Temp. Rise (°F) 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70
Max. Mounting Hgt.
(Ft) 810121214151316181919
Heat Throw Ft.
(Max. Mtg. Hgt.) 29 36 44 44 49 52 47 58 64 67 68
All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor manufacturer and Modine.
All motors are totally enclosed and all single phase motors have built-in thermal overload protection.
Ratings shown are for elevations up to 2,000 ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (In Canada see rating plate.)
Reduction of ratings requires use of a high altitude kit.
Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector hoods.
Voltage 115/60/1 230/60/1 208/60/3 230/60/3 460/60/3 575/60/3
Motor Motor Total Total Motor Total Total Motor Total Total Motor Total Total Motor Total Total Motor Total Total
HP Rpm Amps Amps Watts Amps Amps Watts Amps Amps Watts Amps Amps Watts Amps Amps Watts Amps Amps Watts
1/4 1725 3.7 4.0 466 2.7 2.9 661 1.3 1.5 310 1.2 1.4 316 0.7 0.7 339 0.5 0.5 316
1/3 1725 5.0 5.3 615 2.5 2.7 615 1.2 1.4 290 1.2 1.4 316 0.6 0.7 316 0.8 0.9 500
1/2 1725 8.0 8.3 960 4.0 4.2 960 2.2 2.4 498 2.1 2.3 523 1.1 1.2 546 0.9 1.0 558
3/4 1725 11.0 11.3 1305 5.4 5.6 1282 2.8 3.0 622 2.7 2.9 661 1.4 1.5 684 1.1 1.2 673
1 1725 13.4 13.7 1581 6.7 6.9 1581 3.6 3.8 789 3.5 3.7 845 1.8 1.9 868 1.5 1.5 874
1-1/2 1725 15.2 15.5 1788 7.6 7.8 1788 4.8 5.0 1038 4.8 5.0 1144 2.4 2.5 1144 1.9 2.0 1133
2 1725 --- --- --- --- --- --- 6.8 7.0 1454 6.0 6.2 1420 3.0 3.1 1420 2.3 2.4 1363
3 1725 --- --- --- --- --- --- 9.9 10.1 2099 8.2 8.4 1926 4.1 4.2 1926 3.4 3.5 1995
5 1725 --- --- --- --- --- --- 15.2 15.4 3202 13.0 13.2 3030 6.5 6.6 3030 5.3 5.4 3088