02/02 AWB8230-1447GB
Standard form for user defined
parameter settings
9
PNU Meaning Value range Def. Setpoint
C01 Function of digital input 1 • 00: FWD, clockwise operation
• 01: REV, anticlockwise operation
• 02: FF1, first fixed frequency input
• 03: FF2, second fixed frequency input
• 04: FF3, third fixed frequency input
• 05: FF4, fourth fixed frequency input
• 06: JOG, jog mode
• 09: 2CH, second time ramp
• 11: FRS, controller inhibit
• 12: EXT, external fault
• 13: USP, unattended start protection
• 15: SFT, parameter protection
• 16: AT, input OI is used
• 18: RST, reset
• 19: PTC, PTC thermistor input
(digital input 5 only)
00
C02 Function of digital input 2 Values a PNU C01 01
C03 Function of digital input 3 Values a PNU C01 02
C04 Function of digital input 4 Values a PNU C01 03
C05 Function of digital input 5 Values a PNU C01 18
C11 Digital input 1 • 00: Make contact
• 01: Break contact
00
C12 Digital input 2 Values a PNU C11 00
C13 Digital input 3 Values a PNU C11 00
C14 Digital input 4 Values a PNU C11 00
C15 Digital input 5 Values a PNU C11 00
C21 Signal on digital output 11 • 00: RUN signal
• 01: FA1, frequency reached
• 02: FA2, frequency exceeded
• 03: OL, Overload
• 04: OD, PID deviation exceeded
• 05: AL, fault
01
C22 Signal on digital output 12 Values a PNU C21 00
C23 Indication through FM output • 00: Frequency, analog
• 01: Motor current, analog
• 02: Output frequency pulse signal
00
C31 Digital output 11 • 00: Make contact
• 01: Break contact
01
C32 Digital output 12 • 00: Make contact
• 01: Break contact
01
C33 Relay output K11-K12 (signalling relay) • 00: Make contact
• 01: Break contact
01
C41 Threshold for overload alarm at digital
outputs 11 and 12
0 to 2 x I
e
[A] I
e
C42 Frequency from which FA2 is switched on
during acceleration
0 to 360 Hz 0.0
C43 Frequency from which FA2 is switched off
during deceleration
0 to 360 Hz 0.0
C44 PID control deviation (from the maximum
set point value)
0 to 100 % 3.0