Quick Reference Guide
DF5 Frequency Inverter
02/02 AWB8230-1447GB
8
PNU Meaning Value range Def. Setpoint
b01 Restart mode • 00: Fault message
• 01: 0 Hz start
• 02: Synchronization to current motor speed
and acceleration
• 03: Synchronization and deceleration
00
b02 Permissible power failure duration 0.3 to 25 s 1.0
b03 Waiting time before restart 0.3 to 100 s 1.0
b12 Tripping current for electronic motor
protection device
0.5 to 1.2 x I
e
[A] I
e
(inverter)
b13 Characteristic for electronic motor
protection device
• 00: Enhanced protection
• 01: Normal protection
01
b21 Motor current limitation • 00: Inactive
• 01: Active in every operating status
• 02: Inactive during acceleration,
otherwise active
01
b22 Tripping current for motor current
limitation
0.5 to 1.5 x I
e
[A] I
e
x 1.25
b23 Time constant of motor current limitation 0.1 to 30 Hz/s 1.0
b31 Software dependent parameter
protection
• 00: Through SFT input; all functions inhibited
• 01: Through SFT input; function F01 possible
• 02: Without SFT input; all functions inhibited
• 03: Without SFT input; function F01 possible
01
b32 Magnetizing current 0 to 1.4 x I
e
[A] I
e
x 0.58
b81 Voltmeter compensating value for
FM terminal
0 to 255 80
b82 Increased starting frequency
(e.g. with high level of friction)
0.5 to 9.9 Hz 0.5
b83 Pulse frequency 0.5 to 16 kHz 5.0
b84 Initialization causes • 00: Clearing the fault signal register
• 01: Selection of default settings (default)
00
b85 Operating system • 00: Japan
• 01: European version
• 02:USA
• 03: Reserved
01
b86 Frequency factor for display through
PNU d07
0.1 to 99.9 1.0
b87 OFF key • 00: Always active
• 01: Not active with control through the
FWD/REV terminals
00
b88 Motor restart after removal of the
FRS signal
• 00: At 0 Hz
• 01: At current motor speed
00
b89 Indication when a remote control device
is used
• 01: Actual frequency
• 02: Motor current
• 03: Direction of rotation
• 04: PID actual value
• 05: Status of the digital inputs
• 06: Status of the digital outputs
• 07: Actual frequency times frequency factor
01