Quick Reference Guide
DF5 Frequency Inverter
02/02 AWB8230-1447GB
6
Standard form for user defined parameter settings
The DF5 frequency inverters have programmable parameters. For
a detailed description of the parameters, see the specified page in
the manual (AWB8230-1412GB). In the free Setpoint columns
below, you can list the changes you have made to the default
settings.
PNU Meaning Value range Def. Setpoint
A01 Frequency setpoint input • 00: Potentiometer
• 01: Input O/OI
• 02: PNU F01 or A20
01
A02 Start signal definition • 01: Input FWD/REV
• 02: ON key
01
A03 Base frequency 50 to 360 Hz 50
A04 Maximum end frequency 50 to 360 Hz 50
A11 Frequency with minimum setpoint value 0 to 360 Hz 0
A12 Frequency with maximum setpoint value 0 to 360 Hz 0
A13 Minimum setpoint value 0 to 100 % 0
A14 Maximum setpoint value 0 to 100 % 100
A15 Starting frequency • 00: Apply PNU A11 to motor
• 01: Apply 0 Hz to motor
01
A16 Analog input filter time constant 0 to 8 8
A20 Frequency setpoint definition PNU A01
must be 02
0.5 to 360 Hz 0.0
A21 1st fixed frequency 0.5 to 360 Hz 0.0
A22 2nd fixed frequency 0.5 to 360 Hz 0.0
A23 3rd fixed frequency 0.5 to 360 Hz 0.0
A24 4th fixed frequency 0.5 to 360 Hz 0.0
A25 5th fixed frequency 0.5 to 360 Hz 0.0
A26 6th fixed frequency 0.5 to 360 Hz 0.0
A27 7th fixed frequency 0.5 to 360 Hz 0.0
A28 8th fixed frequency 0.5 to 360 Hz 0.0
A29 9th fixed frequency 0.5 to 360 Hz 0.0
A30 10th fixed frequency 0.5 to 360 Hz 0.0
A31 11th fixed frequency 0.5 to 360 Hz 0.0
A32 12th fixed frequency 0.5 to 360 Hz 0.0
A33 13th fixed frequency 0.5 to 360 Hz 0.0
A34 14th fixed frequency 0.5 to 360 Hz 0.0
A35 15th fixed frequency 0.5 to 360 Hz 0.0
A38 Frequency in jog mode 0.5 to 9.99 Hz 1.0
A39 Motor stop in jog mode through • 00: Coasting
• 01: Deceleration ramp
• 02: DC braking
00
A41 Voltage boost characteristics • 00: Manual
• 01: Automatic
00