08/07 AWB1230-1407GB 5 – 9
Withdrawable unit
Two variations are offered:
Fastening connecting bars:
Conversion from vertical or flange connection to front
connection requires installation of horizontal connection first!
a (page5–11)
(1)
(3)
(4)
(2)
(5)
(1) Standard version: single-hole fitting
(2) Version double-hole fitting
(3) Slots for phase separation walls; mounting position as shown!
(4) Support
(5) Holes o 13.5
85 Nm
85 Nm
(1) (2)
(3)
(4)
(5)
10 Nm 10 Nm
Size 5
Size 5
(1) For
IZM(IN).1-...
IZM(IN).2-...
F 1000 A and
F 2000 A
(2) For
IZM(IN).1-...
IZM(IN).2-...
IZM(IN).3-...
1600 A
2500 A, 3200 A
4000 A
(3) Hexagon socket screw ISO 4762 M6 with strain washer
(4) Support; mounting position as shown!
(5) Coach screw DIN 603 M12 with strain washer and nut