EasyManua.ls Logo

Moeller IZM1 Series - 5.2.3 Front connection

Moeller IZM1 Series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 – 8 08/07 AWB1230-1407GB
5.2.3 Front connection
Note
When front connections are used, a partition between busbar and
arcing space must be fitted on the system side.
Fixed-mounted circuit-breaker
Two variations are offered:
Fastening connecting bars:
(1)
(2)
(3)
(1) Standard version: single-hole fitting
(2) Version double-hole fitting
(3) Holes o 13.5
85 Nm
8 Nm
85 Nm
(1) (2)
(3)
(4)
(5)
(6)
(7)
(8)
8 Nm
(9)
Size 5
Size 5
(1) For
IZM(IN).1-...
IZM(IN).2-...
F 1000 A and
F 2000 A
(2) For
IZM(IN).1-...
IZM(IN).2-...
IZM(IN).3-...
1600 A
2500 A, 3200 A
4000 A
(3) Long connecting bar
(4) Short hexagon socket screw ISO 4762 M6 with strain washer
(5) Short spacer
(6) Coach screw DIN 603 M12 with strain washer and nut
(7) Long distance sleeve
(8) Long hexagon socket screw ISO 4762 M6 with strain washer
(9) Short connecting bar

Related product manuals