5 – 16 08/07 AWB1230-1407GB
5.4 Auxiliary conductor connection
Terminal assignment:
a Circuit diagrams (page 8 1)
Cross section connection type
1) 1 x up to 2.5 mm
2
tubular without plastic sheath to DIN 46228 T1
1 x up to 1.5 mm
2
tubular with plastic sheath to DIN 46228 T2
2 x up to 1.5 mm
2
tubular with plastic sheath, twin ferrules
2) 2 x up to 2.5 mm
2
tubular without plastic sheath to DIN 46228 T1
2 x up to 1.5 mm
2
tubular with plastic sheath to DIN 46228 T2
5.4.1 Plug connector
Arrangement
Retrofitting
Only for circuit-breakers, 1000 V version
Strip conductors
1 x 2 x
Screw terminals
0.5 – 2.5 mm
2
AWG 20...14
+
Wire end ferrule
1)
0.5 – 1.5 mm
2
AWG 20...15
+
Wire end ferrule
1)
Spring-loaded
terminals
0.5 – 2.5 mm
2
AWG 20...14
+
Wire end ferrule
2)
0.5 – 2.5 mm
2
AWG 20...14
+
Wire end ferrule
2)
(1) Arc chute
(2) Plug connector
7 mm
7 mm
X5
X6X7X8
(1)
(2)
COM-DP
(1) Blanking cover
(2) Plug connector
(3) Knife-contact rail adapter for higher arc chute
0173-06
(1)
(2)
1
2
3
4
0173-09
(3)
5
6
0.7 N
m
PH 1