5.3 Connection of main conductors
Main conductor - minimum cross section:
Cleaning the main conductor connection
Cleaning the copper bars
Bolt tight line-side bars
Bracing the main conductors
Frame size Rated current
I
u
Cross section Cu bars
2)
bare/bare black/bare
[A] [mm2]
1)
[mm2]
1)
IZM(IN).1-...
630 1 × 40 × 10 1 × 40 × 10
800 1 × 50 × 10 1 × 60 × 10
1000 1 × 60 × 10 1 × 60 × 10
1250 2 × 40 × 10 2 × 40 × 10
1600 2 × 50 × 10 2 × 50 × 10
IZM(IN).2-...
800 1 × 50 × 10 1 × 50 × 10
1000 1 × 60 × 10 1 × 60 × 10
1250 2 × 40 × 10 2 × 40 × 10
1600 2 × 50 × 10 2 × 50 × 10
2000 3 × 50 × 10 3 × 50 × 10
2500 2 × 100 × 10 2 × 100 × 10
3200 3 × 100 × 10 3 × 100 × 10
IZM(IN).3-...
4000 4 × 100 × 10 4 × 100 × 10
5000 5 × 100 × 10 5 × 120 × 10
6300 6 × 120 × 10 6 × 120 × 10
1) Other Cu bar sizes possible, but the total Cu cross section must not be less.
2) Aluminium bars - please enquire.
ATTENTION
On 4-pole circuit-breakers, the neutral conductor must
always be connected all on the left (front view).
Otherwise this can cause malfunctions of the electronic
overcurrent release.
Connection of cables directly on the circuit-breaker
connections is not permissible.
Circuit-breaker
Steel-wire brush
Metal cuttings
Remove