- 7 -
STEP 2: Mounting the EDR-8010 Series on the wall requires four
screws. Use the EDR-8010 Series with the wall mount plates attached
as a guide to mark the correct location of the four screws. The head of
the screws should be less than 7.0 mm in diameter, and the shaft
should be less than 3.5 mm in diameter.
Wiring Requirements
WARNING
Do not disconnect modules or wires unless power has been
switched off or the area is known to be non
-hazardous. The
devices may only be connected to the supply voltage shown on
the type plate. The devices are designed for operation with a
Safety Extra
-Low
Voltage. Thus, they may only be connected to
the supply voltage connections and to the signal contact with
the Safety Extra
-Low Voltages (SELV) in compliance with
IEC 60950-1/VDE 0805.
ATTENTION
This unit is a built
-
in type. When the unit is installed in another
piece of equipment, the equipment enclosing the unit must
comply with fire enclosure regulation
UL/IEC 62368-1 (or
similar regulation).