8.2.5 BACnet MS/TP, BACnet Ethernet and BACnet Explorer
Max Info Frames the number of transactions the Router may initiate
while it has the MS/TP token. Default is 50.
Max Master the highest MAC address to scan for other MS/TP
master devices. The default of 127 is guaranteed to discover all other
MS/TP master devices on the network.
MAC Address legal values are 0 to 127, must be unique on the
physical network.
Baud Rate the serial baud rate used on the network.
Token Usage Timeout (ms) the number of milliseconds the router
will wait before deciding that another master has dropped the MS/TP
token. This value must be between 20ms and 100ms. Choose a larger
value to improve reliability when working with slow MS/TP devices that
may not be able to meet strict timing specifications.