Matrix
®
E-Series Technical Reference Manual 380V – 480V
21 Form: MAE-TRM-E September 2020 REV. 001
Matrix E-Series 480V Torque Ratings
Table 5-3: Torque Ratings 480V
Filter
Rating
(Amps)
Reactor Terminals
Capacitor Terminals
U4-V4-W4
Input /Output Power
U1-V1-W1 / U2-V2-W2
Reactor
Capacitor
Part Number
Minimum
Interconnect
Wire Gauge
(AWG)
Terminal
Torque
(in-lbs.)
Minimum Wire
Gauge
Terminal
Torque
(in-lbs.)
Terminal
Torque
(in-lbs.)
6 14-6 16 16 CAP-339TP 14 23
8 14-6 16 16 CAP-349TP 14 23
11 14-6 16 16 CAP-365TP 14 23
14 14-6 16 16 CAP-341TP 14 23
21 14-6 16 16 CAP-342TP 14 23
27 14-6 16 16 CAP-343TP 14 23
34 14-6 16 16
12 23
44 14-6 16 16
CAP345TP
12 23
52 Flat copper tab N/A 16 CAP-346TP 10 23
66 Flat copper tab N/A 16
CAP-347TP/
10 23
83 Flat copper tab N/A 16
10 23
103 Flat copper tab N/A 16
CAP-343TP
10 23
128 Flat copper tab N/A N/A CAP-347TP (2) 10 23
165 Flat copper tab N/A N/A
CAP-348TP (2) /
10 23
208 Flat copper tab N/A N/A
CAP-348TP (2) /
CAP-343TP (2)
8 23
240 Flat copper tab N/A N/A
CAP-345TP /
4 23
320 Flat copper tab N/A N/A
CAP-348TP (4) /
2 23
Note: To prevent flexing or bending of the coil windings attached to the flat copper terminal tabs
on the Matrix E-Series reactor, use two wrenches to tighten customer provided cable mounting
hardware.