EasyManua.ls Logo

MTE Matrix E-Series - Matrix E-Series 480 V Torque Ratings; Table 5-3: Torque Ratings 480 V

MTE Matrix E-Series
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Matrix
®
E-Series Technical Reference Manual 380V – 480V
21 Form: MAE-TRM-E September 2020 REV. 001
Matrix E-Series 480V Torque Ratings
Table 5-3: Torque Ratings 480V
Filter
Rating
(Amps)
Reactor Terminals
Capacitor Terminals
U4-V4-W4
Input /Output Power
U1-V1-W1 / U2-V2-W2
Interconnect
Reactor
U4-V4-W4
Capacitor
Part Number
Minimum
Interconnect
Wire Gauge
(AWG)
Terminal
Torque
(in-lbs.)
Recommended
Minimum Wire
Gauge
(AWG)
Terminal
Torque
(in-lbs.)
Terminal
Torque
(in-lbs.)
6 14-6 16 16 CAP-339TP 14 23
8 14-6 16 16 CAP-349TP 14 23
11 14-6 16 16 CAP-365TP 14 23
14 14-6 16 16 CAP-341TP 14 23
21 14-6 16 16 CAP-342TP 14 23
27 14-6 16 16 CAP-343TP 14 23
34 14-6 16 16
CAP-349TP /
CAP-343TP
12 23
44 14-6 16 16
CAP-339TP /
CAP345TP
12 23
52 Flat copper tab N/A 16 CAP-346TP 10 23
66 Flat copper tab N/A 16
CAP-347TP/
CAP-339TP
10 23
83 Flat copper tab N/A 16
CAP-345TP /
CAP-346TP
10 23
103 Flat copper tab N/A 16
CAP-348TP /
CAP-343TP
10 23
128 Flat copper tab N/A N/A CAP-347TP (2) 10 23
165 Flat copper tab N/A N/A
CAP-348TP (2) /
CAP-340TP
10 23
208 Flat copper tab N/A N/A
CAP-348TP (2) /
CAP-343TP (2)
8 23
240 Flat copper tab N/A N/A
CAP-338TP (2) /
CAP-345TP /
CAP-346TP
4 23
320 Flat copper tab N/A N/A
CAP-348TP (4) /
CAP-340TP
2 23
Note: To prevent flexing or bending of the coil windings attached to the flat copper terminal tabs
on the Matrix E-Series reactor, use two wrenches to tighten customer provided cable mounting
hardware.