331 – AL Wiring Cylinder B1
Yellow alarm; warning
Cause Corrective action
Short circuit in cylinder B1
injector wiring. Result: Misfiring.
1. Check injector wiring.
2. Rectify injector solenoid valve short circuit (positive to negative)
(e.g. by exchanging injectors).
3. Fault is rectified when engine is restarted.
332 – AL Wiring Cylinder B2
Yellow alarm; warning
Cause Corrective action
Short circuit in cylinder B2
injector wiring. Result: Misfiring.
1. Check injector wiring.
2. Rectify injector solenoid valve short circuit (positive to negative)
(e.g. by exchanging injectors).
3. Fault is rectified when engine is restarted.
333 – AL Wiring Cylinder B3
Yellow alarm; warning
Cause Corrective action
Short circuit in cylinder B3
injector wiring. Result: Misfiring.
1. Check injector wiring.
2. Rectify injector solenoid valve short circuit (positive to negative)
(e.g. by exchanging injectors).
3. Fault is rectified when engine is restarted.
334 – AL Wiring Cylinder B4
Yellow alarm; warning
Cause Corrective action
Short circuit in cylinder B4
injector wiring. Result: Misfiring.
1. Check injector wiring.
2. Rectify injector solenoid valve short circuit (positive to negative)
(e.g. by exchanging injectors).
3. Fault is rectified when engine is restarted.
335 – AL Wiring Cylinder B5
Yellow alarm; warning
Cause Corrective action
Short circuit in cylinder B5
injector wiring. Result: Misfiring.
1. Check injector wiring.
2. Rectify injector solenoid valve short circuit (positive to negative)
(e.g. by exchanging injectors).
3. Fault is rectified when engine is restarted.