15
Disassembly of cassettes and droplet separators
1
. Remove the distribution header as shown in
2. If a droplet separator has been installed, it is removed in the
same way as the cassettes, see photos above or below.
Great care is to be exercised in handling the humidifier cas-
settes so that the GLASdek material is not damaged. Always
push in, pull out, or lift the cassettes by grasping the metal
frame.
Caution: Spilled water can cause a slippery surface.
3a. If the cassettes are to be removed from the side, first lift up
the guillotine.
3b. Cassettes can also be removed from the open tray side, in
the direction of the airflow.
Restart after service
1
. Shut the bottom valve.
2. Switch on the pump’s safety switch.
3. Check that the snap catches on the top of the distribution
h
eaders are in place. Push the catches downward.
4. Check and adjust, if necessary, the bleed-off flow.