5.2 IMPACT67-P DI8 DO8
Technical data
Number of inputs / outputs .................................. 8
Operating voltage of actuator power supply ...... 24 V ± 25% (18 V to 30.2 V) DC
Operating voltage of sensor power supply ........ 24 V ± 25% (18 V to 30.2 V) DC
Power supply (module electronics) ..................... Via sensor power supply
Incorrect Polarity Protection
System interface ................................................. yes
Digital input yes
Digital output yes
Actuator ............................................................... power supply UA yes
Sensor ................................................................. power supply US yes
Outputs
Quantity ............................................................... 8
Polarity ................................................................ PNP
Voltage ............................................................... 24 VDC
Nominal current 2 A per channel
Overvoltage protection Yes (diode)
Max. switching frequency at ohmic load ............. 50 Hz
Max. switching frequency at inductive load ........ 10 Hz
Short-circuit protection ........................................ Auto. Reset after short-circuit clearance
Inputs
Quantity ............................................................... 8
Polarity ................................................................ PNP
Input characteristic and switch threshold ............ EN 61131-2
Sensor Power Supply
Max. total current ................................................ 9 A (defined by 7/8“)
Supply for sensors .............................................. max. 200 mA for each sensor
Short-circuit protection for sensors ..................... Multifuse
............................................................................ up to 100 mA load automatic start-up
............................................................................ from 100 mA load reset required
Actuator supply
Max. total current ................................................ 9 A (defined by 7/8“)
Short-circuit protection ....................................... Reverse-connect protection
www.comoso.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Murr Elektronik IMPACT67-P and is the answer not in the manual?

Murr Elektronik IMPACT67-P Specifications

General IconGeneral
BrandMurr Elektronik
ModelIMPACT67-P
CategoryControl Unit
LanguageEnglish

Related product manuals