Chapter 6 Troubleshooting 
UD-series Screw Compressors 
6-2 
  Trouble  Direct causes  Factors  Actions 
stops imme-
diately after 
startup. 
 
 
protection circuit 
activated 
 
ant circulation 
volume 
 
If any heat exchange failures as 
typified by poor defrost 
performance, investigate the cause 
For malfunction in pressure 
regulating valve operation, replace 
pressure regulating valve, or 
pressure protection 
device, pressure 
sensor, relays, etc. 
Identify malfunctioning devices, 
examine their causes, and take 
measures. 
Then, replace malfunctioning 
In many cases, motor overload that occurs just after startup is 
caused by the motor, not by the refrigeration cycle. Refer to 
the motor instruction manual. 
low 
pressure 
(low suction 
causes “Low 
pressure protection 
circuit activated” in 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
oil-supply 
pressure   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
element 
*  Big difference in 
outlet/inlet 
pressures 
lubricant 
Remove clogging. Check oil 
contamination level and change 
compressor 
Check oil contamination level. After 
vibration noise diagnosis, overhaul 
amount in oil 
separator 
 
heater, excessive 
refrigerant dissolu-
tion during 
stoppage, thus 
resulting in oil carry 
Inspect relays, etc., on related 
circuits.   
And replace parts as needed. 
return caused by 
insufficient 
refrigerant 
Resolve insufficient volume of 
refrigerant circulation, and then 
return oil from load side heat 
exchanger. 
*  Charge lubricant temporarily. 
clogging in oil 
Remove any causes of trouble to 
restore. 
 
Inspect machine room and around 
compressor and take measures. 
Inspect for presence of oil floating in 
cooling water system. 
If there is any oil floating, check for 
oil leak in oil cooler heat exchanger 
For damage in pipes, etc., caused 
by excessive vibration, take 
vibration reduction measures 
(including sympathetic vibration