NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3 Page 15
FWC-FSLC-EZM1
Addressable SLC single input conventional input module.
Designed to be used with pull stations, water flow switches,
and other applications requiring the monitoring of dry con-
tact alarm initiating devices.
FWC-FSLC-CZM
Addressable SLC single module allows the monitoring of
dry contacts such as pull stations and two-wire convention-
al smoke detectors.
FWC-FSLC-RM2
Addressable SLC Dual Relay Module, provides 2 outputs
while only requiring one SLC address.
FWC-FSLC-ISO
Addressable SLC Fire Isolation Module. Can be used to
meet Class A, Style 7 loop requirements.
FWC-FSLC-SOM1
Addressable SLC Fire Supervised Output Module. Can be
used for output functions such as elevator recall and HVAC
shutdown, or as additional NAC output if used with an addi-
tional power supply.
FWC-FSLC-PULL
Addressable SLC Fire Pull Station.
FWC-FSLC-PROG2
Programmer required for programming address into SLC
devices.
FWC-FSLC-SMK6B
Base required for FWC-FSLC-SMK and FWC-FSLC-HEAT
devices.
Support Products
GEMC-12V2APS-CF
Remote Supervised 12VDC Power Supply. Connects to
Fire Bus, powered by direct 120VAC connection, supports
(2) pair of 12V, 7AH standby batteries.
GEMC-12V2APS-R
Remote Supervised 12VDC Power Supply. Connects to
Burg Bus, powered by supplied 16.5V, 50VA plug-in trans-
former, supports (2) pair of 12V, 7AH standby batteries.
GEMC-NAC7L
GEMC-NAC7S
Remote NAC Extender. Provides four (4) NAC Outputs for
a combined output rating of 6.5A, or a maximum of 2A on
any one output. Includes red enclosure (14"x16"), must be
connected to 120VAC source, supports maximum of 28AH
standby batteries ( (4) pair 12V, 7AH batteries). Connects
to GEMC Fire Bus and is fully supervised. Any or all NAC
outputs may be configured as remote power supply out-
puts. Supports Wheelock and System Sensor NAC syn-
chronization. Maximum of (5) GEMC-NAC7L's or GEMC-
NAC7S's may be added to GEMC control panel, allowing
for a maximum of 20 additional NAC circuits.
ORDERING INFORMATION
OUTPUT ACTIVATION TABLE
"Area 1 General Alarm" Output Activation Table
Outputs can be programmed to activate on a particular event or combination of events using the PCD-Windows
Quickloader NAC/Output Assignment screen, NAC/Output Events tab. The table below details which Alarm
Types and Conditions will activate ("ON") the selected output (selected in the Relay # column in the NAC/Output
Assignment screen) for an Area 1 Gen. Alarm event. For configurations that will not activate the output, an "X" is
shown in the table cell.
OUTPUT EVENT "AREA 1 GENERAL ALARM"
FIRE ZONE
ALARM
(SHORT)
FIRE ZONE
TROUBLE
(OPEN)
WATER-
FLOW ZONE
ALARM
WATER-
FLOW ZONE
TROUBLE
FIRE
SUPERVISORY
ALARM (SHORT)
FIRE
SUPERVISORY
TROUBLE (OPEN)
MONITOR
ZONE
ALARM
(SHORT)
MONITOR
ZONE
ALARM
(OPEN)
FIRE ALARM ON X ON X X X X X
FIRE TROUBLE X ON X ON X ON ON ON
WATERFLOW ALARM X X ON X X X X X
WATERFLOW TROUBLE X X X ON X X X X
SPRINKLER
SUPERVISORY ALARM
X X X X ON X X X
SPRINKLER
SUPERVISORY TROUBLE
X X X X X ON X X
MONITOR ZONE ALARM X X X X X X ON X
MONITOR ZONE TROUBLE X X X X X X X ON