NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3 Page 5
Output Power:
Burg Bell Power: 12VDC Regulated, 2A maximum.
AUX Power: 12VDC Regulated, 750mA maximum.
Burg Bus Power ("Remote Bus Power"): 12V Regulated, 750mA
maximum.
PGM1: Active low, 10.6 - 12VDC @ 150mA.
PGM2: Active low, 10.6 - 12VDC @ 150mA (For UL Commercial in-
stallations)
Aux Relay: Wet 12V Regulated @ 750mA maximum (subtract from
AUX Power); may be set to a dry form "c" relay contact upon removing
the jumper "R"; output rated 30VDC, 3A (Resistive Load)
Total Combined Standby Current (Auxiliary power + Burg Bus power
+ Aux Relay power +25mA standby current): 750mA.
Total Combined Standby and Alarm Current (Auxiliary power + Burg
Bus power + Aux Relay power + Bell power): 2.5A.
GEMC-F8ZCPIM Conventional 8 Fire Zone Expander Module
ELECTRICAL RATINGS
Input Power: 12V Regulated, 120mA standby + total combined
standby and alarm current.
Output Power:
AUX PWR: 12V Regulated, 700mA maximum.
RST PWR: 12V Regulated, 700mA maximum.
Maximum Total Combined Standby and Alarm Current: 120MA +
total combined standby current. Must reduce GEMC-XXXMB total
combined 12V standby power by GEMC-F8ZCPIM total combined
standby current.
Zone Ratings:
Voltage: 13.8 - 8.5VDC.
Current: 2mA standby loop current.
Alarm: 42mA maximum alarm current per zone.
Maximum Loop Resistance: 10 ohms.
Note: Zones not programmed into Area 1 and not wired with an EOLR
will not pull any current in standby or in alarm. All initiating circuits are
Class B.
GEMC-FW-SLC Fire Signaling Line Circuit Module
Electrical Ratings
Input Power:
Power Requirements: 24VDC, 70mA (standby current) + device
current.
Maximum Total Combined 24V Input Current: 475mA.
Output Power: 36V, 150mA maximum. The additional alarm current
(5 LED's @ 8mA for 40mA) is automatically added to determine
standby + alarm current.
Note: Refer to PCD-Windows Quickloader download software's calcu-
lation tools for 24V standby current calculation. GEMC-XXXMB total
combined 24V auxiliary standby current must be reduced by GEMC-
FW-SLC input current.
Operating Temperature: 0°C to 4C
Storage Temperature: 20°C to + 85°C
Dimensions W x D x H: 4.5" x 4" x 1"
GEMC-BSLC Burglary Signaling Line Circuit Module
Electrical Ratings
Input Power:
Power Requirements: 24VDC, 55mA (standby current) + device
current (provided by GEMC Series control panel).
Maximum Total Combined 24V Input Current: 590mA.
Output Power: 16.5V, 500mA maximum.
Note: Refer to PCD-Windows Quickloader download software's calcu-
lation tools for 24V standby current calculation. GEMC-XXXMB total
combined 24V auxiliary standby current must be reduced by GEMC-
BSLC current.
Operating Temperature: 32° to 120°F (0° to 49°C)
Dimensions W x D x H: 4.5" x 4" x 1"
Modules Mounted Inside
the C-Series Motherboard Enclosure:
GEMC-NL-MOD Network Communication Module
Electrical Ratings
Input Power: Nominal 12VDC, 85mA.
Note: 12V power must be supplied from GEMC-XXXMB AUX PWR
terminals. Available panel 12V combined auxiliary current is reduced
by 85mA.
Output Power: PGM-style open collector (negative trigger) with a
maximum sink current of 50mA. Wire only to power-limited circuits less
than 14VDC.
Dimensions: " x 7" x 4¾" (H x W x D)
Note: The GEMC-NL-MOD Network Communication Module can be
used as the primary communicator; see WI1754 for details.
GEMC-RS232 Control Panel / Computer Converter
Electrical Ratings
Input Power: 12.6 - 10.2, 60mA.
Note: 12V power must be supplied from GEMC-XXXMB AUX PWR
terminals. Available GEMC-XXXMB total combined 12V auxiliary cur-
rent must be reduced by 60mA.
Output: RS232 format, maximum 50 feet.
Note: For supplementary use only.
Dimensions (HxWxD) : 11/16" x 2 9/16" x 2 9/16"
Range: 50 feet using RS232 serial cable; 100 feet using Cat5 cable
Note: For supplementary use only.
GEMC-24VR 24 Volt "Regulated" Output Module
Electrical Ratings
Input Power: 24V Unregulated, 2A maximum. Supplied from NAC
output of the GEMC-XXXMB or GEMC-NACXX programmed for re-
versed polarity.
Output Power: 24V Regulated, 1.0A maximum (maximum is reduced
by battery configuration and required standby time).
Dimensions: W = 3.5", L = 4.32", H = 1.15"
Modules Wired to Fire Bus
and/or Burglary Bus:
GEMC-FK1 FIRE KEYPAD
ELECTRICAL RATINGS
Input Power: 12VDC nominal, 110mA maximum, 35mA if backlighting
is disabled (cut jumpers W1, W2 & W3).
Maximum Number of Fire Keypads: 7
Maximum Number of Fire Keypads + Burglary Keypads: 15
POWER RATINGS
GEMC-FK1 is powered by the Fire bus of the GEMC-Series mother-
board, GEMC-12V2APS or an appropriately rated UL Listed Security/
Signaling power limited power supply. Deduct these values from the
system standby current, as described in the control panel wiring dia-
gram.
GEMC-BK1 BURGLARY KEYPAD
ELECTRICAL RATINGS
Input Power: 12.5 - 7.5VDC, 110mA maximum (120mA when using
integral EZM). 35mA if backlighting is disabled (cut jumpers W1, W2 &
W3).
Output Power:
PGM Output (active low): 5mA, 12V. Wiring to power limited circuits
less than 14VDC.
Maximum Number of Burglary Keypads: 15.
Maximum Number of Fire Keypads + Burglary Keypads: 15.
Maximum Wiring Length for each run: (#22AWG): 1000' divided by
total number of keypads on run.
POWER RATINGS
GEMC-FK1 and GEMC-BK1 are both powered by the keypad bus of
the control panel, GEMC-12V2APS or an appropriately rated UL Listed
Security/Signaling power-limited power supply. Deduct these values
from the system standby current, as described in the control panel
wiring diagram.

Table of Contents