GEM-P1632 Installation Instructions
WI808F 8/03
!
Page 39
can be assigned to any of the 8 available external relays. Multiple relay events can drive the same External Relay.
Relay Follows Zone
External Relays can be programmed to follow a zone. If values are entered in Time locations, the relay will time out after the
programmed time.
Remote Panic
See Panic Zone
Report Digital Dialer Exit Error/Recent Closing
(SIA CP-01 Requirement: 4.2.2.6)
A Recent Closing transmission is sent if an alarm occurs within two (2) minutes after the expiration of the Exit Time. If the user number is
available, it is included in the Recent Closing transmission.
Note:
Recent Closing transmissions are not sent for fire alarms.
Report Telco 1; Report Telco 3 (Double or Split Reporting)
Alarms, alarm restores, troubles and trouble restores may be selected individually for each zone. Violation of a zone selected to report
will communicate the code(s) selected for that zone to the central station.
Normally, Report Telco 1 is used to report to the central station. Report Telco 3 is used when certain zones will report to a different
receiver (split reporting); Report Telco 1 and Report Telco 3 are both used on the same zone to report to two receivers successively
(Double Reporting). (Double Reporting requires a successful report to Telco 1 before reporting to Telco 3.) Also see Backup Report on
Telco 2.
Reset Day Zone with Arm/Disarm Only
See Day Zone
Residential Fire
Prevents battery depletion during alarm. Must be programmed in UL Residential Fire Installations.
Select Alarm Output for Keyfob Chirp (Address 0721, Bit 7)
This feature is associated with Chirp Output on Keyfob Arm/Disarm (Address 0720-Bit 6). Normally the chirp on a keyfob arm/disarm is
transmitted to the PGM2 output. Selecting "Select Alarm Output for Keyfob Chirp" causes the "Bell" to chirp instead of the PGM2 upon re-
mote arming.
Sensor Watch
It supervises designated zones for a lack of activity and will cause a system trouble E-22-XX Sensor Activity Fail if no activity is
detected for the programmed period of time. The sensor watch should be determined based on the coverage area while disarmed and
calculated using the least amount of traffic.
Note:
requires version 9 or later.
Silencing Alarm Area
In any system, the ability to silence any combination of alarm devices (outputs) initiated from any area. This must be programmed for
all systems to be able to silence an alarm. For example, in a two-area system, each area could be programmed to silence only those
alarms initiated within its own area; or both areas could be programmed to silence an alarm initiated from either area.
Silence All Outputs During Audio Session See Veri-Phone™ Audio Priority Over Alarms
Single-Digit Format
See Central Station Receiver Data Format
Smoke Detectors; 2-Wire Smoke Detectors; Wireless Smoke Low Battery Resound
Connect smoke detectors as shown in the diagrams. The “Fire Power” (Terminal 25) is used to reset the smoke detectors.
Two-Wire Smoke Detectors
Two-wire smoke detectors may be used only on Zones 7 and 8. Up to 10 compatible 2-wire smoke detectors may be wired to each
zone. In Residential applications, program Pulse Alarm Output. Zones 7 and 8 have been designed so they can be easily configured as
2-wire smoke detector zones by means of jumpers (JP3) located above Terminal 21.
1. Program Zones 7 and/or 8 for 2-Wire Smoke Detectors and Fire.
2. If Zone 7 is selected as a 2-Wire Fire Zone, move the left jumper on JP3 from the top two pins (BURG) to the bottom two
pins (2WF).
3. Similarly, if Zone 8 is selected as a 2-Wire Fire Zone, move the right jumper on JP3 from the top two pins (BURG) to the
bottom two pins (2WF).
4. Connect 2-wire smoke detectors to Zones 7 and/or 8 as shown in the GEM-P1632 Installation Instructions (WI808).
Four-Wire Smokes
If installing 4-wire smokes, subtract smoke-detector alarm current from available standby current. See COMPATIBLE UL-LISTED
DEVICES.
Wire 4-wire smokes as shown in the GEM-P1632 Installation Instructions (WI808). Program each zone for Fire. Also program zones for
Pulse Alarm Output. If they are of the self-resetting type, 4-wire smokes may be powered from Terminals 25 and 6.
Wireless Smokes
Wireless Smoke Low Battery Resound allows smoke detectors to sound off every 4 hours to indicate low battery voltage and the need
for replacement. (Required for UL Installations)
Sound Alarm On Exit Error (SIA CP-01 Requirement: 4.2.2.4)
An Exit Error sequence is initiated if an entry/exit zone is violated at the expiration of the Exit Time. An Exit Error is processed as follows:
Glossary

Other manuals for NAPCO Gemini GEM-P1632

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NAPCO Gemini GEM-P1632 and is the answer not in the manual?

NAPCO Gemini GEM-P1632 Specifications

General IconGeneral
BrandNAPCO
ModelGemini GEM-P1632
CategoryControl Panel
LanguageEnglish

Related product manuals