Steps
1. Reboot the BMC if the replacement module is not the same model as the old module:
a. From the LOADER prompt, change to advanced privilege mode: set privilege advanced
b. Reboot the BMC: sp reboot
2. From the LOADER prompt, reboot the node: bye
This reinitializes the I/O cards and other components and reboots the node.
Be sure to exit Maintenance mode after completing the conversion.
3. Return the node to normal operation: storage failover giveback -ofnode impaired_node_name
4. If automatic giveback was disabled, reenable it: storage failover modify -node local -auto-giveback true
Step 4: Return the failed part to NetApp
Return the failed part to NetApp, as described in the RMA instructions shipped with the kit. See the Part Return
& Replacements
page for further information.
Replace a power supply - AFF A70, AFF A90
Replacing a power supply (PSU) involves disconnecting the target PSU from the power
source, unplugging the power cable, removing the old PSU and installing the replacement
PSU, and then reconnecting it to the power source.
The power supplies are redundant and hot-swappable.
About this task
This procedure is written for replacing one PSU at a time.
Do not mix PSUs with different efficiency ratings or different input types. Always replace like for
like.
Use the appropriate procedure for your type of PSU: AC or DC.