[ENG] UniPing server solution v4/SMS & UniPing server solution v3, User guide -[USS] Sensors Plugin
[USS] Sensors Plugin
–
Electricity Meter "Energy MeterCE102"
An electricity meter is connected by a two-wire line according to the table:
Meter Socket UniPing server solution v4/SMSTerminal Block
11 (В) RS485-
12 (А) RS485+
Buzzer (mod.STD-3025)
Connecting the buzzer to the RELAY (NO - is normally opened contact, NC - is normally closed contact) with using
+12V:
Loop Color UniPing server solution v4/SMS,UniPingserver solution v3 Terminal Block
Black GND
Red NO (RELAY)
+12V ↔ Middle contact (RELAY)
A sensor is packaged with an inseparable cable, withconnectors on the ends. A cable length can be increased with
the help offlat cable extenders of RC-4sensor, which are sequentially plugged one into another. Or it can be done
independently with the help of any wire with a minimum cross section of 0,4 mm
2
. Maximum allowable length of a
flat cable is 100 m.