PUMP(S) ON:
The display will show ‘O’ - off or ‘I’ - on.The pump(s) will turn
off automatically when the water is below the pump dis-
charge level.
Note: When on battery power and the time remaining is near
exhaustion, the pump(s) may continue to run for approximately
1 minute before turning off.
PUMP
WAS ACTIV
ATED: (Backup Mode Only)
If either pump was activated the display will show ‘A or ‘a’ for the
corresponding pump. If the pump location is blinking the alarm is
in the silence mode. An ‘Activated Pump’ alerts that the NexPump
was needed. This may indicate the failure of the AC pump or
other primary pump that the NexPump unit is backing up. It may
also indicate that the incoming water was at a flow that the pri-
mary pump could not handle and the NexPump was needed for
additional discharge capacity. After determining the source of
the problem, clear the failed condition by depressing and
holding the function button for 1 second, while the ‘C’ is in
the last location of the display release the function button.
The display will show ‘Alarm Cleared’ and return to normal.
PUMP
REPLACEMENT
Displayed as ‘R’ or ‘r. Pump has reached average life span.
Pump may still be operational however should be replaced at
this time. Clear the condition by depressing and holding the
function button for 1 second, while the ‘C’ is in the last loca-
tion of the display release
the function button. The display will show
‘Alarm Cleared’.
Note: Write down which pump has been flagged as
replace. Once cleared there is no user available method
to retrieve the replace flag information.
PUMP
FUSE
Each pump is protected by a 25-Amp ATC Type Fuse. The fuses are
located inside the NexPump unit and can be accessed by the panel
on the bottom. The power should be removed before attempting
removal of the panel. The pump fuses are located towards the fan
and are clear plastic with a 25 stamped on them. The Pump 2 fuse is
closest to the access panel, while Pump 1 is directly above. If a fuse
blows, check for possible obstructions or frayed wires on the failed
pump. It may also indicate a failed pump.
This side intentionally blank
10