S-series VVM S / SMO S
These settings are made on the display on the indoor mod-
ule/control module.
MENU 7.3.2 - INSTALLED HEAT PUMP
Here, you make specific settings for the installed heat pump.
Cooling permitted
Setting range: on/off
Silent mode permitted
Setting range: on/off
Max. frequency 1
Setting range: 25 120 Hz
Max. frequency 2
Setting range: 25 120 Hz
Compressor phase
Setting range F2050 1 x 230 V: L1, L2, L3
Detect compressor phase
Setting range F2050 1 x 230 V: off/on
Current limit
Setting range F2050 1 x 230 V: off/on
Max. current
Setting range F2050 1 x 230 V: 6 32 A
Stop temperature compressor
Setting range -20 -2 °C
blockFreq 1
Setting range: on/off
From frequency
Setting range: 25 117 Hz
To frequency
Setting range: 28 120 Hz
blockFreq 2
Setting range: on/off
From frequency
Setting range: 25 117 Hz
To frequency
Setting range: 28 120 Hz
Cooling permitted: Here, you can set whether the cooling
function will be activated for the heat pump.
Silent mode permitted: Here, you set whether silent mode
will be activated for the heat pump. Please note that you
now have the option to schedule when silent mode will be
active.
The function should only be used for limited periods, because
F2050 possibly may not reach its dimensioned output.
Detect compressor phase: This shows in which phase the
heat pump detected that you have F2050 230V~50Hz. Phase
detection normally occurs automatically in connection with
start-up of the indoor module/control module. This setting
can be changed manually.
Current limitation: Here, you set whether the current lim-
itation function will be activated for the heat pump, if you
have F2050 230V~50Hz. During active function, you can
limit the value of the maximum current.
BlockFreq 1: Here, you can select a frequency range within
which the heat pump is not permitted to work. This function
can be used if certain compressor speeds cause disturbing
noise in the house.
BlockFreq 2: Here, you can select a frequency range within
which the heat pump is not permitted to work.
33Chapter 7 | Control Heat pump EB101NIBE F2050