May be due toDescriptionAlarm text on the displayAlarm
Defective fan motor
Defective circuit board for inverter in F2050
Continuous deviation on power transistor for
15 minutes.
Inverter error265
Service valve closed
Loose connection sensor (BT15, BT3)
Defective sensor (BT15, BT3)
Too little refrigerant
Insufficient refrigerant is detected upon start-
up in cooling mode.
Insufficient refrigerant266
Defective circuit board for inverter in F2050
Defective control board in F2050
Compressor fault
Failed start for compressorInverter error267
Sudden power failureOvercurrent, Inverter A/F moduleInverter error268
Cold weather conditions
Sensor fault
Temperature of BT28 below the value that per-
mits operation
Cold outdoor air271
Warm weather conditions
Sensor fault
Temperature of BT28 above the value that
permits operation
Hot outdoor air272
Open circuit or short circuit on sensor input
Sensor does not work (see section "Disturb-
ances in comfort")
Defective control board in F2050
Sensor fault, heat exchanger in F2050(Tho-R).Sensor fault Tho-R277
Open circuit or short circuit on sensor input
Sensor does not work (see section "Disturb-
ances in comfort")
Defective control board in F2050
Sensor fault, outdoor temperature sensor in
F2050 (Tho-A).
Sensor fault Tho-A278
Open circuit or short circuit on sensor input
Sensor does not work (see section "Disturb-
ances in comfort")
Defective control board in F2050
Sensor fault, hot gas in F2050 (Tho-D).Sensor fault Tho-D279
Open circuit or short circuit on sensor input
Sensor does not work (see section "Disturb-
ances in comfort")
Defective control board in F2050
Sensor fault, suction gas in F2050 (Tho-S).Sensor fault Tho-S280
Open circuit or short circuit on sensor input
Sensor does not work (see section "Disturb-
ances in comfort")
Defective control board in F2050
Fault in the refrigerant circuit
Sensor fault, low pressure transmitter in F2050.Sensor fault LPT281
Outdoor module and indoor module are not
compatible.
Heat pump and indoor module do not function
together properly due to technical parameters.
Non-compatible air/water
heat pump
294
Open circuit or short circuit on sensor inputSensor fault, Sensor high pressure heating/low
pressure cooling in F2050 (BP4).
Sensor fault BP4404
Sensor does not work (see section "Disturb-
ances in comfort")
Defective control board AA23 in F2050