106F2050
Output data according to EN 14 511, partial load
1
7.18 / 2.93 / 2.455.55 / 2.05 / 2.71-7 / 35 °CHeating
Capacity / power input / COP (kW/kW/-) at nominal flow
Outdoor temp: / Supply temp.
3.46 / 0.83 / 4.172.31 / 0.56 / 4.132 / 35 °C
3.24 / 1.12 / 3.242.02 / 0.67 / 3.012 / 45 °C
4.00 / 0.75 / 5.332.64 / 0.49 / 5.427 / 35 °C
5.00 / 1.28 / 3.912.43 / 0.65 / 3.747 / 45 °C
7.07 / 2.40 / 2.955.32 / 1.94 / 2.7435 / 7 °CCooling
Capacity / power input / EER (kW/kW/-) at maximum flow
Outdoor temp: / Supply temp.
10.79 / 3.00 / 3.607.55 / 2.11 / 3.5835 / 18 °C
SCOP according to EN 14825
6.3 / 6.55.20 / 5.60kWNominal heat output (P
designh
) average climate 35 °C / 55 °C (Europe)
6.5 / 6.25.80 / 5.70kWNominal heat output (P
designh
) cold climate 35 °C / 55 °C
6.9 / 6.65.57 / 5.48kWNominal heat output (P
designh
) warm climate 35 °C / 55 °C
4.6 / 3.45.08 / 3.58SCOP average climate, 35 °C / 55 °C (Europe)
3.9 / 2.94.10 / 3.05SCOP cold climate, 35 °C / 55 °C
6.4 / 4.46.76 / 4.55SCOP warm climate, 35 °C / 55 °C
Energy rating, average climate
2
A++ / A++A+++ / A++The product’s room heating efficiency class 35 C / 55 C
3
A+++ / A++The system’s room heating efficiency class 35 C / 55 C
4
Electrical data
230 V ~ 50 Hz, 230 V 2 ~ 50 HzRated voltage
1615A
rms
Max operating current, heat pump
1514A
rms
Max operating current, compressor
8650WMax. power, fan
1616A
rms
Fuse
IP24Enclosure class
Refrigerant circuit
R32Type of refrigerant
675GWP refrigerant
1.841.3kgVolume
Twin RotaryType of compressor
1.240.88tCO
2
-equivalent (The cooling circuit is hermetically sealed.)
4.15 (41.5)-MPa (bar)Cut-out value pressure switch HP (BP1)
0.079 (0.79)-MPa (bar)Cut-out value pressure switch LP (BP2)
Airflow
3,0002,530m
3
/hMax airflow
Working area
-20 / 43°CMin./max. air temperature, heating
15 / 43°CMin./max. air temperature, cooling
Reverse cycleDefrosting system
Heating medium circuit
0.6 (6.0)MPa (bar)Max system pressure heating medium
0.12 – 0.380.08 – 0.32l/sRecommended flow interval, heating operation
0.15 – 0.380.11 – 0.29l/sRecommended flow interval, cooling operation
0.19l/sMin. design flow, defrosting (100% pump speed)
25 / 58°CMin./max. HM temp, continuous operation
G1 (Ø28 mm)Connection heating medium F2050 external thread
G1 (Ø28 mm)Connection heating medium flex pipe
20 (22)DN (mm)Min. recommended pipe dimension (system)
Dimensions and weight
1,035993mmWidth
422383mmDepth
895 (+10/-0)781 (+10/-0)mmHeight with stand
8376kgNet weight
Miscellaneous
064 318064 328Part no.
1
Power statements including defrosting according to EN 14511 at heating medium supply corresponding to DT=5 K at 7 / 45.
2
Reported efficiency for the system also takes the temperature regulator into account. If the system is supplemented with an external auxiliary boiler or
solar heating, the total efficiency of the system must be recalculated.
3
Scale for the product’s room heating efficiency class A++ to G. Control module model SMO S
4
Scale for the system’s room heating efficiency class A+++ to G. Control module model SMO S
45Chapter 12 | Technical dataNIBE F2050