Switching to maximum electrical output
If more than the maximum power (7 kW) for the immersion
heater connected on delivery is needed, the heat pump can
be switched to maximum 9 kW.
Move white cable from terminal block X7-2:N to terminal
block X9:L(2) on the base board (AA2).
3x400 V (maximum electrical power,
connected upon delivery 7 kW för S1255-12 /
-16)
Max phase
current L3(A)
Max phase
current L2(A)
Max phase
current L1(A)
Max electric-
al addition
(kW)
0
4.31
8.72
4.38.73
8.78.74
13.08.75
8.78.78.76
13.08.78.77
1
1
Factory setting
3x400 V (maximum electrical power,
connected to 9 kW for S1255-12 / -16)
Max phase
current L3(A)
Max phase
current L2(A)
Max phase
current L1(A)
Max electric-
al addition
(kW)
0
8.72
8.78.74
8.78.78.76
15.615.68.79
3x400 V, S1255-6
Max phase
current L3(A)
Max phase
current L2(A)
Max phase
current L1(A)
Max electric-
al addition
(kW)
0.0
2.20.5
4.31.0
4.32.21.5
8.72.0
8.72.22.5
8.74.33.0
8.74.32.23.5
7.511.54.0
7.511.52.24.5
15.67.55.0
15.67.52.25.5
15.611.56.0
15.611.52.26.5
1
1
Factory setting
3x230 V, S1255-6
Max phase
current L3(A)
Max phase
current L2(A)
Max phase
current L1(A)
Max electric-
al addition
(kW)
0.0
2.22.20.5
4.34.31.0
6.56.51.5
8.78.72.0
10.910.92.5
11.54.38.73.0
13.26.58.73.5
15.18.78.74.0
17.010.98.74.5
1
1
Factory setting
3x230 V, S1255-12
Max phase
current L3(A)
Max phase
current L2(A)
Max phase
current L1(A)
Max electric-
al addition
(kW)
0
8.78.72
15.18.78.74
15.115.115.16
27.227.215.19
1
1
Factory setting
1x230 V S1255-6
Max phase current L1(A)Max electric-
al addition
(kW)
0.0
2.20.5
4.31.0
6.51.5
8.72.0
10.92.5
13.03.0
15.23.5
17.44.0
19.64.5
1
1
Factory setting
1x230 V, S1255-12
Max phase current L1(A)Max electric-
al addition
(kW)
0.0
4.31.0
8.72.0
13.03.0
17.44.0
21.75.0
26.16.0
30.47.0
1
1
Factory setting
When the current sensors are connected, S1255 monitors
the phase currents and allocates the power steps automat-
ically to the least loaded phase.
NIBE S1255Chapter 5 | Electrical connections26