Control - Heat pump
EB101
S-SERIES VVM S / SMO S
These settings are made on the display on the indoor
module/control module.
Menu 7.3.2 - Installed heat pump
Here, you make specific settings for the installed heat
pump.
Silent mode permitted
Setting range: on/off
Max. frequency 1
Setting range: 25 120 Hz
Max. frequency 2
Setting range: 25 120 Hz
Compressor phase
Setting range S2125 1 x 230 V: L1, L2, L3
Detect compressor phase
Setting range S2125 1 x 230 V: off/on
Current limit
Setting range S2125 1 x 230 V: off/on
Max. current
Setting range S2125 1 x 230 V: 6 32 A
blockFreq 1
Setting range: on/off
From frequency
Setting range: 25 117 Hz
To frequency
Setting range: 28 120 Hz
blockFreq 2
Setting range: on/off
From frequency
Setting range: 25 117 Hz
To frequency
Setting range: 28 120 Hz
Defrosting
Start manual defrosting
Setting range: on/off
Start temperature for defrost function
Setting range: -3 3 °C
Cut-out value activation passive defrosting
Setting range: 2 10 °C
Defrost more often
Alternatives: Yes / No
Silent mode permitted: Here, you set whether silent
mode is to be activated for the heat pump. Please note
that you now have the option to schedule when silent
mode will be active.
The function should only be used for limited periods,
because S2125 possibly may not reach its dimensioned
output.
NIBE S2125Chapter 7 | Control36