5.
Press the OK or Back button to exit read off mode.
TIP
Wait 24 hours before making a new setting, so that the room temperat-
ure has time to stabilise.
If it is cold outdoors and the room temperature is too low, increase the
curve slope by one increment.
If it is cold outdoors and the room temperature is too high, lower the
curve slope by one increment.
If it is warm outdoors and the room temperature is too low, increase
the curve offset by one increment.
If it is warm outdoors and the room temperature is too high, lower the
curve offset by one increment.
external adjustment
climate system 1
external adjustment1.9.2
climate system
Setting range: -10 to +10 or desired
room temperature if the room
sensor is installed.
Default value: 0
Menu
1.9.2
Connecting an external contact, for example, a room thermostat or a timer
allows you to temporarily or periodically raise or lower the room temper-
ature while heating. When the contact is on, the heating curve offset is
changed by the number of steps selected in the menu. If a room sensor is
installed and activated the desired room temperature (°C) is set.
NIBE™ SMO 20Chapter 3 | SMO 20 at your service32