min. flow line temp.
climate system 1
°C
min. flow line temp. heating1.9.3.1
heating
Setting range: 5-70 °C
Default value: 20 °C
cooling (heat pump with
cooling function required)
Depending on which cooling func-
tion (2 pipe /4 pipe-system) is used,
the lower limit of the setting range
can vary from 7 to 18 °C.
Setting range: 7-30 °C
Factory setting: 18 °C
Menu
1.9.3
In menu 1.9.3 you select heating or cooling, in the next menu (min. supply
temp.heating/cooling) set the minimum temperature on the supply tem-
perature to the climate system. This means that SMO 20 never calculates
a temperature lower than that set here.
If there is more than one climate system the setting can be made separately
for each system.
TIP
The value can be increased if you have, for example, a cellar that you
always want to heat, even in summer.
You may also need to increase the value in "stop heating" menu 4.9.2
"auto mode setting".