COMMUNICATION WITH HEAT PUMP
Connect the heat pump (EB101) with a screened three
core cable to terminal block X4:1 (A), X4:2 (B) and X4:3
(GND) on the accessory board (AA5) as illustrated.
If several heat pumps are to be connected to SMO 40
these must be connected in cascade as illustrated.
Caution
Up to 8 heat pumps can be controlled by
SMO 40.
Caution
It is possible to combine various NIBE air/water
heat pumps, of different sizes and models, with
each other, effective from software version
8319.
With an earlier software version (than version
8319), an air/water heat pump with an inverter-
controlled compressor can only be combined
with other inverter-controlled heat pumps of
the same model.
Connecting to the heat pump