op. prioritisation
RS SULRULWLVDWLRQ 
PLQ
PLQ
PLQ
KRW ZDWHU
KHDWLQJ
SRRO



op. prioritisation
Setting range: 0 to 180 min
Default value: 30 min
Choose here how long the installation should work with each requirement
if there are several requirements at the same time. If there is only one re-
quirement the installation only works with that requirement.
The indicator marks where in the cycle the installation is.
If 0 minutes is selected it means that requirement is not prioritised, but
will only be activated when there is no other requirement.
Menu
4.9.1
auto mode setting
VWDUW FRROLQJ
VWRS KHDWLQJ
VWRS DGGLWLRQDO KHDW
ILOWHULQJ WLPH
r&
r&
r&
KUV
DXWR PRGH VHWWLQJ 
start cooling
Setting range: -20 40 °C
Default value: 25
stop heating
Setting range: -20 40 °C
Default values: 17
stop additional heat
Setting range: -25 40 °C
Default values: 5
filtering time
Setting range: 0 48 h
Default value: 24 h
Menu
4.9.2
When the operating mode is set to "auto", the indoor module selects when
start and stop of additional heat and heat pr oduction is permitted, depend-
ent on the average outdoor temperature. If accessories for cooling are
present or if the heat pump has the integrated cooling function and it is
activated in the menu you can also select the start temperature f or cooling.
NIBE™ VVM 310Chapter 3 | VVM 310 at your service52