EN
10 – English
The control unit has 3 keys OPEN (s), STOP (Set), CLOSE (t) (Fig. 49) that
can be used both for controlling the unit during testing and for programming
the available functions.
The programmable functions available are divided into 2 levels and their relative
operating status is displayed by
means of the 8 LEDs (L1 ... L8)
on the control unit.
LED SIGNALS:
• Led lit = function active;
• Led off = function not active.
PROGRAMMING KEYS:
• OPEN (s): the “OPEN” key en-
ables control of pole opening or
can be used, during program-
ming, to move the programming
point up.
• STOP (Set): the “STOP” key enables the user to stop the manoeuvre; if
pressed for more than 5 seconds, it enables entry to programming mode.
• CLOSE (t): the “CLOSE” key enables control of pole closing or can be used,
during programming, to move the programming point down.
IMPORTANT! – During a manoeuvre (open or close) all 3 keys (s, Set,
t) work as STOP; causing the maneuver underway to stop or the re-
verse of the maneuver.
6.1 - Level one programming (ON-OFF functions)
All the level 1 functions (Table 6) are set by default to “OFF” and may be modi-
edatanytimeasexplainedinTable 7. The parameters can be set on a scale
from 1 to 8. To check the value corresponding to each led see Table 6.
IMPORTANT – In the programming procedure, the maximum time interval
that can elapse between activation of one key and the next is 10 seconds.
When this time elapses, the procedure terminates automatically, memorising
themodicationsmadeupuntilthen.
CONTROL UNIT PROGRAMMING
6
IMPORTANT – In the programming procedure, the maximum time interval
that can elapse between activation of one key and the next is 10 seconds.
When this time elapses, the procedure terminates automatically, memorising
themodicationsmadeupuntilthen.
6.2 - Level two programming (adjustable parameters)
All level 2 parameters are set by default (Table 8)andmaybemodiedatany
time as explained in Table 9.
The parameters can be set on a scale from 1 to 8. To check the value corre-
sponding to each led see Table 8.
Open
Stop
Set
Close
L1
Close
Open
PP
Stop
Bluebus
2
L2
L3
L4
L5
L6
L7
L8
BusT4
Open
Stop
Set
Close
TABLE 6 - First level functions
Led Description Example
L1
Automatic closure
This function performs automatic closure of the pole after the programmed pause time. Factory setting: 20 seconds. Value
programmable from 3 to 60 seconds.
L2
Reclose after photo
This function enables the pole to remain in Opening position for the time required for transit. When the function is active,
operation depends on the parameter set in the function “Automatic closure”:
• with “Automatic closure” active, the Opening manoeuvre stops immediately after the photocells are disengaged and the
Closure manoeuvre starts after 5 seconds.
• with “Automatic closure” not active, the pole always reaches the maximum Opening position (even if the photocells are
disengaged beforehand) and Closure starts after 5 seconds.
L3
Always close
This function is useful in the event of a power failure, even brief. In fact if this function is active (ON), when power is restored,
the control unit detects the pole as open and starts Closure. For reasons of safety the Closure manoeuvre is preceded by a
3-secondpre-ashinginterval.
L4
Stand by
This function allows consumptions to be reduced. If active, 1 minute after the end of the manoeuvre, the control unit turns off
theTXoftheBluebusphotocellsandalltheLEDS,excludingtheBluebusledwhichashesmoreslowly.Whenthecontrol
unit receives a command normal operation is restored. For the use of the barrier with the Solemyo system it is neces-
sary to activate an even deeper “Stand by” mode, the “Stand by all”. This operation is performed using the Oview
programmer.
L5
Long/short deceleration
This function enables the user to double the space for starting deceleration, both in Opening and Closing. If the function is
deactivated, deceleration is short.
L6
Automatic start-up
This parameter, if active (ON), lets you activate the start-up (starting at maximum speed) until the pole is made to move. The
default value is “OFF”.
L7
Modo Slave
By activating this function the barrier becomes “Slave”: it is possible to synchronize the operation of 2 counterposed barriers
where one works as Master and the other as Slave; for more information see paragraph 7.6 - Master-Slave Mode.
L8
Direction of motor rotation
This parameter enables inversion of the direction of motor rotation to enable barrier installation on the right; the factory setting
is “OFF” (standard motor rotation – pole closure on left). Important – If the function is activated, the Opening and Clos-
ing positions must be memorised again (Paragraph 4.5).
TABLE 7 - Programming procedure (first level functions)
01. Press and hold down the “Set” key for approx. 3 seconds;
02. Release the key when led L1 starts flashing;
03. Press keys “s” or “t” to move from the flashing led to the led associated with the function to be modified;
04. Press “Set” to change the status of the function: (short flash = OFF; long flash = ON);
05. Wait 10 seconds (maximum time) to exit the programming mode.
Note – During this procedure, points 03 and 04 need to be repeated when programming other functions to “ON” or “OFF” during the phase itself.
SET
SET
SET
L1
/
3 s
10 s