NE200/300 Series Drive User Manual
Chapter 6 Parameter description 137
the sum of leakage inductance of stator and leakage inductance of rotor.
After motor rated power (F5.02) is changed, the drive will automatically
change F5.03~F5.09 to adapt to the rated motor power.
F5.10 Auto tune Range: 0~2【0】
0: No operation
1: Static tuning, it is suitable to the situation as the motor is not easy to
disconnect from the load.
Action description: Set the function code to 1 and press RUN key for
confirmation, and then the drive will conduct static tuning.
2: Rotary tuning
To ensure the dynamic control performance of the drive, please select
rotary
tuning. During the rotary tuning, the motor must be disconnected with
the loads (i.e. no-load).
Action description:
Set the function code to 2 and press RUN key for confirmation, the
drive will conduct static rotary first, and then accelerate to 80% of
motor rated frequency according to the acceleration time set in F0.19,
holding this frequency for a while, and finally decelerate to zero speed
according to deceleration time set in F0.20.
F5.11 Synchronous motor stator
resistor Rs
【
】
:
②
1~65535mΩ
③
1~65535mΩ (for drive
0.1~6553.5mΩ (for drive>22kW)
F5.12 Synchronous motor D-axis
inductance Ld
【Depends on model】Range:
②
0.01~655.35mH
③
0.01~655.35mH (for drive≤30kW)
0.001~65.535mH(for drive>22kW)
F5.13 Synchronous motor Q-axis
inductance Lq
【Depends on model】Range:
②
0.01~655.35mH